Mdec speed demand source, Mdec engine rpm request, Volvo accelerator pedal position – Basler Electric DGC-2020 User Manual
Page 489: Volvo rpm select, J1939 start stop config, Ecu settling time, Ecu pulse cycle time, Ecu disconnect time, Ecu connect time, Mtu request test overspeed
9400200990 Rev X
DGC-2020 Modbus
™ Communication
B-57
Register
Description
Type
Units
Scaling
Factor
R/W
Range
45262
MDEC Speed Demand
Source
Uint32
N/A
N/A
RW
0 = Analog CAN
1 = Up Down ECU
2 = Up Down CAN
3 = Analog ECU
4 = Frequency
5 = No CAN Demand
45264
MDEC Engine RPM
Request
Uint32
N/A
N/A
RW
1400 - 2000
45266
Volvo Accelerator Pedal
Position
Uint32
N/A
N/A
RW
0 - 100
45268
Volvo RPM Select
Uint32
N/A
N/A
RW
0 = Primary
1 = Secondary
45270
J1939 Start Stop Config
Uint32
N/A
N/A
RW
0 = Standard
1 = Volvo Penta
2 = MTU MDEC
3 = MTU ADEC
4 = MTU ECU7
5 = GM
6 = Cummins
7 = MTU Smart Connect
8 = Scania
9 = John Deere
45272
ECU Settling Time
Uint32
Millisecond
Milli
RW
5500 - 30000
45274
ECU Pulse Cycle Time
Uint32
Minute
N/A
RW
1 - 60
45276
ECU Disconnect Time
Uint32
Second
N/A
RW
1 - 60
45278
ECU Connect Time
Uint32
Second
N/A
RW
1 - 60
45280
MTU Request Test
Overspeed
Uint32
N/A
N/A
RW
0 = Off
1 = On
45282
MTU Governor
Switchover Parameters
Uint32
N/A
N/A
RW
0 - 1
45284
MTU Intermittent Oil
Prime Request
Uint32
N/A
N/A
RW
0 = Off
1 = On
45286
MTU Trip Info Reset
Request
Uint32
N/A
N/A
RW
0 = Off
1 = On
45288
MTU Speed Increase
Uint32
N/A
N/A
RW
0 = Off
1 = On
45290
MTU Speed Decrease
Uint32
N/A
N/A
RW
0 = Off
1 = On
45292
MTU Speed Demand
Limit Boolean
Uint32
N/A
N/A
RW
0 = Off
1 = On
45294
MTU Mode Switch
Uint32
N/A
N/A
RW
0 - 1000
45296
MTU Increased Idle
Uint32
N/A
N/A
RW
0 - 1000
45298
MTU Gov Param Set
Select
Uint32
N/A
N/A
RW
0 = Off
1 = On
45300
MTU Fan Override
Uint32
N/A
N/A
RW
0 = Off
1 = On
45302
MTU Prime On Engine
Start
Uint32
N/A
N/A
RW
0 = Off
1 = On
45304
MTU CAN Rating SW1
Uint32
N/A
N/A
RW
0 = Off
1 = On
45306
MTU CAN Rating SW2
Uint32
N/A
N/A
RW
0 = Off
1 = On
45308
MTU Disable Cylinder
Cutout 1
Uint32
N/A
N/A
RW
0 = Off
1 = On
45310
MTU Cylinder Cutout 2
Uint32
N/A
N/A
RW
0 = Off
1 = On
45312
MTU ECU7 Module
Type Data
Int32
N/A
N/A
RW
0 = Off
1 = On
45314
RESERVED
45316
MTU NMT Alive Repeat
Milliseconds
Int32
Millisecond
N/A
RW
100 - 500