1 phase overcurrent curve(51-2), 1 phase overcurrent alarm configuration (51-2), 3 phase undervoltage pickup (27-2) – Basler Electric DGC-2020 User Manual
Page 461: 3 phase undervoltage activation delay (27-2), 3 phase undervoltage inhibit frequency (27-2), 3 phase undervoltage alarm configuration (27-2), 1 phase undervoltage pickup (27-2), 1 phase undervoltage activation delay (27-2), 1 phase undervoltage inhibit frequency (27-2), 1 phase undervoltage alarm configuration (27-2)

9400200990 Rev X
DGC-2020 Modbus
™ Communication
B-29
Register
Description
Type
Units
Scaling
Factor
R/W
Range
44332
1 Phase Overcurrent Curve
(51-2)
Uint32
N/A
N/A
RW
0 = S1 Curve
1 = S2 Curve
2 = L1 Curve
3 = L2 Curve
4 = D Curve
5 = M Curve
6 = I1 Curve
7 = I2 Curve
8 = V1 Curve
9 = V2 Curve
10 = E1 Curve
11 = E2 Curve
12 = A Curve
13 = B Curve
14 = C Curve
15 = G Curve
16 = F Curve
17 = Programmable
44334
1 Phase Overcurrent Alarm
Configuration (51-2)
Uint32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
44336
3 Phase Undervoltage Pickup
(27-2)
Uint32
Volt
N/A
RW
70 - 1000
44338
3 Phase Undervoltage Activation
Delay (27-2)
Uint32
Decisecond
Deci
RW
0 - 300
44340
3 Phase Undervoltage Inhibit
Frequency (27-2)
Uint32
Hertz
N/A
RW
20 - 400
44342
3 Phase Undervoltage Alarm
Configuration (27-2)
Uint32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
44344
1 Phase Undervoltage Pickup
(27-2)
Uint32
Volt
N/A
RW
70 - 1000
44346
1 Phase Undervoltage Activation
Delay (27-2)
Uint32
Decisecond
Deci
RW
0 - 300
44348
1 Phase Undervoltage Inhibit
Frequency (27-2)
Uint32
Hertz
N/A
RW
20 - 400
44350
1 Phase Undervoltage Alarm
Configuration (27-2)
Uint32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
44352
3 Phase Overvoltage Pickup
(59-2)
Uint32
Volt
N/A
RW
70 - 1000
44354
3 Phase Overvoltage Activation
Delay (59-2)
Uint32
Decisecond
Deci
RW
0 - 300
44356
3 Phase Overvoltage Alarm
Configuration (59-2)
Uint32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
44358
1 Phase Overvoltage Pickup
(59-2)
Uint32
Volt
N/A
RW
70 - 1000
44360
1 Phase Overvoltage Activation
Delay (59-2)
Uint32
Decisecond
Deci
RW
0 - 300
44362
1 Phase Overvoltage Alarm
Configuration (59-2)
Uint32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
44364
Overcurrent Low Line Scale
Factor (51-2)
Float
N/A
N/A
RW
0.001 - 3
44366
Overvoltage Low Line Scale
Factor (59-2)
Float
N/A
N/A
RW
0.001 - 3
44368
Undervoltage Low Line Scale
Factor (27-2)
Float
N/A
N/A
RW
0.001 - 3
44370
Phase Imbalance Hysteresis
Uint32
Volt
N/A
RW
1 - 5
44372
3 Phase Undervoltage
Hysteresis (27-1)
Uint32
Volt
N/A
RW
1 - 60