Rtc minute, Rtc second, Rtc month – Basler Electric DGC-2020 User Manual
Page 452: Rtc day, Rtc year, Rtc dst enable, Gen pt primary, Gen pt secondary, Gen ct primary, Bus pt primary
B-20
DGC-2020 Modbus
™ Communication
9400200990 Rev X
Register
Description
Type
Units
Scaling
Factor
R/W
Range
43524
RTC Minute
Int32
Minute
N/A
RW
0 - 59
43526
RTC Second
Int32
Second
N/A
RW
0 - 59
43528
RTC Month
Int32
N/A
N/A
RW
1 - 12
43530
RTC Day
Int32
N/A
N/A
RW
1 - 31
43532
RTC Year
Int32
N/A
N/A
RW
0 - 99
43534
RTC DST Enable
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
43536
Gen PT Primary
Int32
Volt
N/A
RW
1 - 99999
43538
Gen PT Secondary
Int32
Volt
N/A
RW
1 - 480
43540
Gen CT Primary
Int32
Amp
N/A
RW
1 - 9999
43542
Bus PT Primary
Int32
Volt
N/A
RW
1 - 99999
43544
Bus PT Secondary
Int32
Volt
N/A
RW
1 - 480
43546
Cranking Style
Uint32
N/A
N/A
RW
0 = Continuous
1 = Cycle
43548
Number of Crank Cycles
Uint32
N/A
N/A
RW
1 - 7
43550
Cycle Crank Time
Unit32
Second
N/A
RW
5 - 15
43552
Continuous Crank Time
Unit32
Second
N/A
RW
5 - 60
43554
Crank Disconnect Limit
Uint32
Percent
N/A
RW
10 - 100
43556
Pre Crank Delay
Uint32
Second
N/A
RW
0 - 30
43558
Configured Gen Connection
Uint32
N/A
N/A
RW
0 = Delta
1 = Wye
2 = 1-phase AB
3 = 1-phase AC
4 = Grounded Delta
43560
Gen Rated Frequency
Int32
Hertz
N/A
RW
0 = 50 Hz
1 = 60 Hz
43562
Rated kW
Uint32
kiloWatt
N/A
RW
5 - 9999
43564
Rated Engine RPM
Uint32
RPM
N/A
RW
750 - 3600
43566
No Load Cool Down Time
Uint32
Minute
N/A
RW
0 - 60
43568
EPS Current Threshold
Int32
PercentCTPri
N/A
RW
3 - 10
43570
Fuel Level Function
Uint32
N/A
N/A
RW
0 = Disable
1 = Fuel Lvl
2 = Natural Gas
3 = Propane
43572
Number Flywheel Teeth
Uint32
N/A
N/A
RW
1 - 500
43574
Speed Signal Source
Uint32
N/A
N/A
RW
1 = MPU
2 = Gen Freq
3 = MPU Freq
43576
NFPA Level
Uint32
N/A
N/A
RW
0 = Zero
1 = One
2 = Two
43578
Horn Enable
Int32
N/A
N/A
RW
0 = Disabled
1 = Enabled
43580
Single Phase Override Sensing
Uint32
N/A
N/A
RW
0 = AB
1 = AC
43582
RESERVED
43584
LCD Contrast Value
Uint32
N/A
N/A
RW
0 - 100
43586
Front Panel Sleep Mode
Uint32
N/A
N/A
RW
0 = Disabled
1 = Enabled
43588
RESERVED
43590
UTC Offset
Int32
Minute
N/A
RW
(-1440) - 1440
43592
DST Configuration
Int32
N/A
N/A
RW
0 = Disabled
1 = Floating
2 = Fixed
43594
Start/End Time Reference
Int32
N/A
N/A
RW
0 = Local Time
1 = UTC Time
43596
DST Bias Hours
Int32
N/A
N/A
RW
0 - 23
43598
DSP Bias Minutes
Int32
N/A
N/A
RW
0 - 59