Name

Description

Symbol

Status Input

ATS Input

True when the ATS (Auto Transfer Switch) input is
true or the ATS logic element is true.

Status Input

Audible Horn

True when the Audible Horn is active.

Status Input

Auto Mode

True when the DGC-2020 is in Auto Mode or the
Auto Mode logic element is true.

Status Input

Auto Restart

True when the Automatic Restart function is active.

Status Input

Battery Charger
Fail

True when the Battery Charger Fail input is true.

Status Input

Battle Override

True when the Battle Override input is true.

Status Input

Bus Dead

True when the Bus Dead condition settings have
been exceeded.

Status Input

Bus Fail

True when the Bus Fail condition settings have been
exceeded.

Status Input

Bus Forward
Rotation

True when the sensed bus phase rotation matches
the bus phase rotation specified in the system
settings.

Status Input

Bus Reverse
Rotation

True when the sensed bus phase rotation differs
from the bus phase rotation specified in the system
settings.

Status Input

Bus Stable

True when the Bus Stable condition settings have
been exceeded.

Status Input

CANBus Bus Off

True when the CANBus bus is off.

Status Input

CANBus Error
Passive

True when a passive error is annunciated by the
CANBus.

Status Input

Configurable
Elements 1-8

True when the Configurable Element x logic element
is true.

Status Input

Configurable
Protection 1-8

True when the Configurable Protection x Over
Threshold #1 is true. (Over 1 shown.)

Status Input

Contact
Expansion
Module

Contact Expansion Module Connected. True when
an optional CEM-2020 is connected to the DGC-
2020.

9400200990 Rev X

DGC-2020 BESTlogic

Plus Programmable Logic

5-3