Basler Electric DGC-2020 User Manual
Page 232

Name
Description
Symbol
Status Input
Cool Down Timer
Active
True when the Cool Down Timer is timing out. The
Cool Down Timer is true under two circumstances:
1. The unit is in auto and ATS is removed,
causing the DGC-2020 to go into a
cooldown state.
2. The engine is running (in RUN or AUTO
mode with ATS applied) and the load has
been removed (i.e. the EPSSUPLOAD
status input is false due to small load). If the
load is reapplied, the Cool Down Timer
stops and resets, and it will restart when the
load is removed the next time.
Status Input
DPF Lamp
Command
True when DPF lamp is lit. This status input mimics
the state of the DPF lamp. It remains true when the
DPF lamp is constantly lit and toggles true and false
at a rate of 1 Hz when DPF lamp is blinking.
Status Input
Emergency Stop
True when the Emergency Stop button has been
pressed.
Status Input
Engine Running
True while the Engine is Running.
Status Input
EPS Supplying
Load
True while the EPS is supplying load.
Status Input
Front Panel
Buttons
True while the AUTO front panel button is pressed.
Status Input
Front Panel
Buttons
True while the DOWN front panel button is pressed.
Status Input
Front Panel
Buttons
True while the EDIT front panel button is pressed.
Status Input
Front Panel
Buttons
True while the LAMP TEST front panel button is
pressed.
Status Input
Front Panel
Buttons
True while the LEFT front panel button is pressed.
Status Input
Front Panel
Buttons
True while the OFF front panel button is pressed.
Status Input
Front Panel
Buttons
True while the RESET front panel button is pressed.
Status Input
Front Panel
Buttons
True while the RIGHT front panel button is pressed.
Status Input
Front Panel
Buttons
True while the RUN front panel button is pressed.
Status Input
Front Panel
Buttons
True while the ALARM SILENCE front panel button
is pressed.
5-4
DGC-2020 BESTlogic
™
Plus Programmable Logic
9400200990 Rev X