Basler Electric DGC-2020 User Manual
Page 572

B-140
DGC-2020 Modbus
™ Communication
9400200990 Rev X
Holding
Register
Parameter
Range
Read/Write
Supported
Data
Format
Units
40223
Activation Time Delay Maximum 10
R -
Seconds
40224
Activation Time Delay Stepsize
1
R -
Seconds
WEAK BATTERY VOLTAGE PRE-ALARM
40225
Enable
0-1
R W
0 =Off
1 =On
40226
Threshold
40-80 (12V)
80-160 (24V)
R W
.1 VoltDC
40227
Minimum
40 / 80
R -
.1 VoltDC
40228
Maximum
80 / 160
R -
.1 VoltDC
40229
Stepsize
1 (0.1 VoltDC)
R -
.1 VoltDC
40230
Pre-alarm Activation Time Delay 1-10
R W
Seconds
40231
Activation Time Delay Minimum 1
R -
Seconds
40232
Activation Time Delay Maximum 10
R -
Seconds
40233
Activation Time Delay Stepsize
1
R -
Seconds
LOGON PASSWORD (40252-7)
HIGH COOLANT TEMPERATURE ALARM
40281
Enable
0-1
R W
0 =Off
1 =On
40282
Shutdown Enable
0-1
R W
0 =Off
1 =On
40283
Threshold
100-280
R W
DegF
40284
Minimum
100
R -
DegF
40285
Maximum
280
R -
DegF
40286
Stepsize
1
R -
DegF
40287
Arming Delay after Crank
Disconnect
60
R W
Seconds
40288
Arming Delay Minimum
60
R -
Seconds
40289
Arming Delay Maximum
60
R -
Seconds
40290
Arming Delay Stepsize
0
R -
Seconds
LOW OIL PRESSURE ALARM
40291
Enable
0-1
R W
0 =Off
1 =On
40292
Shutdown Enable
0-1
R W
0 =Off
1 =On
40293
Threshold
3-100
R W
PSI
40294
Minimum
3
R -
PSI
40295
Maximum
100
R -
PSI
40296
Stepsize
1
R -
PSI
40297
Arming Delay after Crank
Disconnect
5-15
R W
Seconds
40298
Arming Delay Minimum
5
R -
Seconds
40299
Arming Delay Maximum
15
R -
Seconds
40300
Arming Delay Stepsize
1
R -
Seconds
OVERSPEED ALARM
40301
Enable
0-1
R W
0 =Off
1 =On
40302
Shutdown Enable
0-1
R W
0 =Off
1 =On
40303
Threshold
105-140
R W
% of Rated
40304
Minimum
105
R -
% of Rated
40305
Maximum
140
R -
% of Rated
40306
Stepsize
1
R -
% of Rated