Alarms, Alarms -57, High coolant temperature – Basler Electric DGC-2020 User Manual
Page 167

A
High Fuel Level: Enable or Disable, threshold is adjustable from 0 to 150% in 1% increments. Activation
delay is adjustable from 0 to 30 s in 1 s increments.
B
Low Battery Voltage: Enable or Disable, threshold is adjustable from 6 to 14 Vdc (12 Vdc battery) or 12
to 28 Vdc (24 Vdc battery) in 0.1 Vdc increments. Activation delay is adjustable from 1 to 60 s in 1 s
increments.
C
Weak Battery Voltage: Enable or Disable, threshold is adjustable from 4 to 14 Vdc (12 Vdc battery) or 8
to 28 Vdc (24 Vdc battery) in 0.1 Vdc increments. Activation time delay is adjustable from 0 to 10 s in 0.1
s increments.
D
Battery Overvoltage: Enable or Disable, threshold is adjustable from 12 to 32 Vdc in 0.1 Vdc
increments.
E
Maintenance Interval: Enable or Disable, threshold is adjustable from 0 to 5,000 hrs in 1 hr increments.
F
Engine kW Overload: Enable or Disable, threshold is adjustable from 0 to 200% of Genset kW Rating in
1% increments.
G
Low Fuel Level: Enable or Disable, threshold is adjustable from 10 to 100% in 1% increments.
H
High Coolant Temp: Enable or Disable, threshold is adjustable from 100 to 280
°F or 38 to 138°C in 1°
increments. Activation time delay is fixed at 60 s.
I
Low Coolant Temp: Enable or Disable, threshold is adjustable from 0 to 151
°F or -18 to 66°C in 1°
increments.
J
Low Coolant Level: Enable or Disable, threshold is adjustable from 1 to 99% in 1% increments.
K
Low Oil Pressure: Enable or Disable, threshold is adjustable from 2.9 to 150 psi in 0.1 psi increments,
0.2 to 10.3 bar in 0.1 bar increments, or 20 to 1,034.5 kPa in 0.1 kPa increments. Activation time delay is
fixed at 10 s.
L
ECU Comm Failure: Enable or Disable.
M
Active DTC: Enable or Disable.
N
AVR Bias Output Limit: Enable or Disable, activation delay is adjustable from 1 to 15 s in 1 s
increments.
O
GOV Bias Output Limit: Enable or Disable, activation delay is adjustable from 1 to 15 s in 1 s
increments.
P
Intergenset Comm Failure: Enable or Disable.
Q
LSM Comm Failure: Enable or Disable.
R
ID Missing: Enable or Disable.
S
ID Repeat: Enable or Disable.
T
CEM Comm Failure: Enable or Disable.
U
AEM Comm Failure: Enable or Disable.
V
Checksum Failure: Enable or Disable.
W
Synchronizer Failure: Enable or Disable.
X
Breaker Close Failure: Enable or Disable.
Y
Monitor: Transitions Only or Always.
Z
Breaker Open Failure: Enable or Disable.
AA
Monitor: Transitions Only or Always.
BB
Reverse Rotation: Enable or Disable.
Alarms
An alarm is annunciated when a condition programmed to trigger an alarm is detected. When an alarm
condition exists, the front panel Alarm indicator lights, the Horn output (if programmed and enabled)
energizes, and the cause of the alarm is displayed on the front panel LCD. An alarm condition stops the
engine by opening the Fuel output contact. Alarms are reset when the DGC-2020 is set to Off mode.
Each DGC-2020 alarm is described in the following paragraphs. Alarms can be enabled and adjusted in
BESTCOMSPlus or through the front panel HMI.
The BESTCOMSPlus Alarms screen is illustrated in Figure 4-49.
High Coolant Temperature
High coolant temperature alarm settings
A
consist of an enable/disable setting and a threshold setting. If
enabled, a high coolant temperature alarm is triggered after a four second delay when the engine coolant
temperature exceeds the threshold setting. The arming delay disables the high coolant temperature alarm
function for a user-adjustable time during engine startup. System units are configured on the System
Settings screen.
9400200990 Rev X
DGC-2020 BESTCOMSPlus
® Software
4-57