Dtc enable, Rings for modem answer, Modem offline delay – Basler Electric DGC-2020 User Manual
Page 457: Modbus baud rate, Modbus parity, Modbus address, Modem dialout conditions 3, Lsm-2020 enable, Dhcp enabled, Reserved

9400200990 Rev X
DGC-2020 Modbus
™ Communication
B-25
Register
Description
Type
Units
Scaling
Factor
R/W
Range
44034
DTC Enable
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
44036
Rings for Modem Answer
Int32
N/A
N/A
RW
1 - 9
44038
Modem Offline Delay
Int32
Minute
N/A
RW
1 - 240
44040
Modbus Baud Rate
Int32
N/A
N/A
RW
0 = 9600 Baud
1 = 4800 Baud
2 = 2400 Baud
3 = 1200 Baud
44042
Modbus Parity
Int32
N/A
N/A
RW
0 = No Parity
1 = Odd Parity
2 = Even Parity
44044
Modbus Address
Int32
N/A
N/A
RW
1 - 247
44046-47
Modem Dialout Conditions 3
Uint32
N/A
N/A
RW
Bit 0 = 78 Vector Shift Trip
Bit 1 = 51-3 Trip Pre-Alarm
Bit 2 = 51-3 Trip Alarm
Bit 3 = Duplicate AEM
Bit 4 = AEM Comms Failure
Bit 5 = Duplicate CEM
Bit 6 = CEM Comms Failure
Bit 7 = Duplicate LSM
Bit 8 = Config Element 8 Status
Bit 9 = Config Element 7 Status
Bit 10 = Config Element 6 Status
Bit 11 = Config Element 5 Status
Bit 12 = Config Element 4 Status
Bit 13 = Config Element 3 Status
Bit 14 = Config Element 2 Status
Bit 15 = Config Element 1 Status
Bit 16 = ID Repeat
Bit 17 = ID Missing
Bit 18 = LSM Comms Failure
Bit 19 = Intergenset Comms Failure
Bit 20 = GOV Output Limit
Bit 21 = AVR Output Limit
Bit 22 = Auto Restart Fail Alarm
Bit 23 = kW Overload 3 Pre-Alarm
Bit 24 = kW Overload 2 Pre-Alarm
Bit 25 = 40 Trip Pre-Alarm
Bit 26 = 32 Trip Pre-Alarm
Bit 27 = 59-2 Trip Pre-Alarm
Bit 28 = 27-2 Trip Pre-Alarm
Bit 29 = 51-2 Trip Pre-Alarm
Bit 30 = 40 Trip Alarm
Bit 31 = 32 Trip Alarm
44048
LSM-2020 Enable
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
44050
DHCP Enabled
Uint32
N/A
N/A
R
0 = Disabled
1 = Enabled
44052-56
RESERVED
44058
CEM-2020 Enable
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
44060
RESERVED
44062
AEM-2020 Enable
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
44064
CEM Outputs
Int32
N/A
N/A
RW
0 = 18 Outputs
1 = 24 Outputs