Basler Electric DGC-2020 User Manual
Page 534

B-102
DGC-2020 Modbus
™ Communication
9400200990 Rev X
Register
Description
Type
Units
Scaling
Factor
R/W
Range
46600
AEM Input 7 Under 1
Threshold
Int32
Centi Unit
Centi
RW
(-100000000) – 99999900
46602
AEM Input 7Under 2
Threshold
Int32
Centi Unit
Centi
RW
(-100000000) – 99999900
46604
AEM Input 7 Over 1
Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
46606
AEM Input 7 Over 2
Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
46608
AEM Input 7 Under 1
Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
46610
AEM Input 7 Under 2
Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
46612
AEM Input 7 Out of
Range Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
46614
AEM Input 8 Max
Voltage
Int32
DeciVolt
Deci
RW
0 - 100
46616
AEM Input 8 Max
Current
Int32
Milliamp x 10
Deci
RW
40 - 200
46618
AEM Input 8 Min
Voltage
Int32
DeciVolt
Deci
RW
0 - 100
46620
AEM Input 8 Min
Current
Int32
Milliamp x 10
Deci
RW
40 - 200
46622
AEM Input 8 Param Max
Int32
Centi Unit
Centi
RW
(-100000000) – 99999900
46624
AEM Input 8 Param Min
Int32
Centi Unit
Centi
RW
(-100000000) – 99999900
46626
AEM Input 8 Hysteresis
Int32
Deci Percent
Deci
RW
0 – 1000
46628
AEM Input 8 Arming
Delay
Int32
Second
N/A
RW
0 – 300
46630
AEM Input 8 Threshold
1 Activation Delay
Int32
Second
N/A
RW
0 – 300
46632
AEM Input 8 Threshold
2 Activation Delay
Int32
Second
N/A
RW
0 – 300
46634
AEM Input 8 Over 1
Threshold
Int32
Centi Unit
Centi
RW
(-100000000) – 99999900
46636
AEM Input 8Over 2
Threshold
Int32
Centi Unit
Centi
RW
(-100000000) – 99999900
46638
AEM Input 8 Under 1
Threshold
Int32
Centi Unit
Centi
RW
(-100000000) – 99999900
46640
AEM Input 8Under 2
Threshold
Int32
Centi Unit
Centi
RW
(-100000000) – 99999900
46642
AEM Input 8 Over 1
Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
46644
AEM Input 8 Over 2
Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
46646
AEM Input 8 Under 1
Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
46648
AEM Input 8 Under 2
Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only