Basler Electric DGC-2020 User Manual
Page 550
B-118
DGC-2020 Modbus
™ Communication
9400200990 Rev X
Register
Description
Type
Units
Scaling
Factor
R/W
Range
47046
AEM1 RTD2 Under1
Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only
47048
AEM1 RTD2 Under2
Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only
47050
AEM1 RTD2 Out of
Range Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only
47052
AEM1 RTD3 Hysteresis
Int32
DeciPercent
Deci
RW
0 - 1000
47054
AEM1 RTD3 Arming
Delay
Int32
Second
N/A
RW
0 - 300
47056
AEM1 RTD3 Threshold1
Activation Delay
Int32
Second
N/A
RW
0 - 300
47058
AEM1 RTD3 Threshold2
Activation Delay
Int32
Second
N/A
RW
0 - 2
47060
AEM1 RTD3 Over1
Threshold
Int32
Deg F
N/A
RW
-58 - 482
47062
AEM1 RTD3 Over2
Threshold
Int32
Deg F
N/A
RW
-58 - 482
47064
AEM1 RTD3 Under1
Threshold
Int32
Deg F
N/A
RW
-58 - 482
47066
AEM1 RTD3 Under2
Threshold
Int32
Deg F
N/A
RW
-58 - 482
47068
AEM1 RTD3 Over1
Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only
47070
AEM1 RTD3 Over2
Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only
47072
AEM1 RTD3 Under1
Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only
47074
AEM1 RTD3 Under2
Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only
47076
AEM1 RTD3 Out of
Range Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only
47078
AEM1 RTD4 Hysteresis
Int32
DeciPercent
Deci
RW
0 - 1000
47080
AEM1 RTD4 Arming
Delay
Int32
Second
N/A
RW
0 - 300
47082
AEM1 RTD4 Threshold1
Activation Delay
Int32
Second
N/A
RW
0 - 300
47084
AEM1 RTD4 Threshold2
Activation Delay
Int32
Second
N/A
RW
0 - 2
47086
AEM1 RTD4 Over1
Threshold
Int32
Deg F
N/A
RW
-58 - 482
47088
AEM1 RTD4 Over2
Threshold
Int32
Deg F
N/A
RW
-58 - 482
47090
AEM1 RTD4 Under1
Threshold
Int32
Deg F
N/A
RW
-58 - 482
47092
AEM1 RTD4 Under2
Threshold
Int32
Deg F
N/A
RW
-58 - 482