Basler Electric DGC-2020 User Manual
Page 577

9400200990 Rev X
DGC-2020 Modbus
™ Communication
B-145
Holding
Register
Parameter
Range
Read/Write
Supported
Data
Format
Units
40472
Enable
0-1
R W
0 =Off
1 =On
40473
Threshold
3-100
R W
PSI
LOW BATTERY VOLTAGE PRE-ALARM
40474
Enable
0-1
R W
0 =Off
1 =On
40475
Threshold
60-120 (12V)
120-240 (24V)
R W
.1 VoltDC
40476
Pre-alarm Activation Time Delay 1-10
R W
Seconds
WEAK BATTERY VOLTAGE PRE-ALARM
40477
Enable
0-1
R W
0 =Off
1 =On
40478
Threshold
40-80 (12V)
80-160 (24V)
R W
.1 VoltDC
40479
Pre-alarm Activation Time Delay 1-10
R W
Seconds
HIGH COOLANT TEMPERATURE ALARM
40480
Enable
0-1
R W
0 =Off
1 =On
40481
Shutdown Enable
0-1
R W
0 =Off
1 =On
40482
Threshold
100-280
R W
DegF
40483
Arming Delay after Crank
Disconnect
60
R W
Seconds
LOW OIL PRESSURE ALARM
40484
Enable
0-1
R W
0 =Off
1 =On
40485
Shutdown Enable
0-1
R W
0 =Off
1 =On
40486
Threshold
3-100
R W
PSI
40487
Arming Delay after Crank
Disconnect
5-15
R W
Seconds
OVERSPEED ALARM
40488
Enable
0-1
R W
0 =Off
1 =On
40489
Shutdown Enable
0-1
R W
0 =Off
1 =On
40490
Threshold
105-140
R W
% of Rated
40491
Alarm Activation Time Delay
0-500
R W
MilliSec
SENDER FAIL ALARMS
40492
Coolant Temperature Sender
Failure Alarm Enable
0-1
R W
0 =Off
1 =On
40493
Oil Pressure Sender Failure
Alarm Enable
0-1
R W
0 =Off
1 =On
40495
Magnetic Pick-up Failure
Alarm Enable
0-1
R W
0 =Off
1 =On
40496
Loss of Generator Voltage Alarm
Enable
0-1
R W
0 =Off
1 =On
40497
Pre-alarm Buzzer Enable
0-1
R W
0 =Off
1 =On
40498
Battery Charger Failure
Pre-alarm Enable
0-1
R W
0 =Off
1 =On
40499
Global Sender Failure Alarm
Time Delay
0-10
R W
Seconds
CRANKING PARAMETERS
40500
Cranking Style
0-1
R W
0=Contin.
1=Cycle
40501
Number of Crank Cycles
1-7
R W
40502
Cycle Crank Time
5-15
R W
Seconds
40503
Continuous Crank Time
1-60
R W
Seconds