Figure 7-50. Settings Explorer, BESTlogicPlus Programmable Logic (Step 12)

13. Next, click on the I/O tab, drag the inputs assigned in step 3 above to the main logic, and connect

them to the appropriate input or output of the Generator Breaker block. Note the “Open Gen Breaker”
and “Close Gen Breaker” are inputs to the generator breaker block, and are used to request a
breaker open or close through contact inputs. The “Gen 52 Open” and “Gen 52 Close” are outputs
from the DGC-2020 to the physical breaker. The DGC-2020 opens or closes the generator breaker
through these control signals. See Figure 7-51.

7-44

DGC-2020 Setup

9400200990 Rev X