Single phase detect threshold, Start relay control, Run relay control – Basler Electric DGC-2020 User Manual
Page 454: Prestart relay control, Single phase connect generator detection, Off mode cool down enable, Reserved, Not in auto horn enable, Clock not set warning enable, Alternate frequency

B-22
DGC-2020 Modbus
™ Communication
9400200990 Rev X
Register
Description
Type
Units
Scaling
Factor
R/W
Range
43642
Single Phase Detect Threshold
Int32
Volt
N/A
RW
0 - 480
43644
Start Relay Control
Uint32
N/A
N/A
RW
0 = Predefined
1 = Programmable
43646
Run Relay Control
Uint32
N/A
N/A
RW
0 = Predefined
1 = Programmable
43648
Prestart Relay Control
Uint32
N/A
N/A
RW
0 = Predefined
1 = Programmable
43650
Single Phase Connect
Generator Detection
Int32
N/A
N/A
RW
0 = A-B
1 = A-C
43652
Off Mode Cool Down Enable
Uint32
N/A
N/A
RW
0 = Disable
1 = Enable
43654
RESERVED
43656
Not In Auto Horn Enable
Uint32
N/A
N/A
RW
0 = Disable
1 = Enable
43658
Clock Not Set Warning Enable
Uint32
N/A
N/A
RW
0 = Disable
1 = Enable
43660
Alternate Frequency
Int32
Hertz
Centi
RW
1000 - 45000
43662
Generator System Type
Int32
N/A
N/A
RW
0 = Single Generator
1 = Multiple Generator
43664
Gen CT Low Line Scale Factor
Float
N/A
N/A
RW
0.001 - 3
43666
Metric Pressure Units
Int32
N/A
N/A
RW
0 = Bar
1 = kPa
43668
System Units
Int32
N/A
N/A
RW
0 = English
1 = Metric
43670
Kpa bar Config Data
Int32
N/A
N/A
RW
0 = Bar
1 = Kpa
43672
Crank Disconnect Pressure Bar
Data
Int32
Bar
Deci
RW
2 - 103
43674
RPM Bandwidth Data
Int32
N/A
N/A
RW
0 - 1000
43676
Number Flywheel Teeth
Uint32
N/A
Deci
RW
10 - 5000
43678
Phase Rotation
Int32
N/A
N/A
RW
0 = ACB
1 = ABC
43680
Restart Delay
Int32
Second
N/A
RW
0 - 120
43682
Configured Bus Connection
Uint32
N/A
N/A
RW
0 = Single Phase
1 = Three Phase
43684
Fuel Level Source
Int32
N/A
N/A
RW
1 – 9
43686
Fuel Level Percent Max
Int32
N/A
N/A
RW
0 – 150
43688
Fuel Level Percent Min
Int32
N/A
N/A
RW
0 – 150
43690
Cycle Rest Time
Uint32
Second
N/A
RW
5 - 15
43692
Rated Volts - Low Line Scale
Factor Data
Float
N/A
N/A
RW
0.001 - 3
43694-748
FUTURE USE
Control
Register
Description
Type
Units
Scaling Factor
R/W
Range
43750
Emergency Stop: Writing a 1 will
toggle emergency stop from off
to on. Writing a 1 again will
toggle emergency stop from on
to off
Int32
N/A
N/A
RW
1 = Toggle On/Off
43752
Remote Start
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
43754
Remote Stop
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
43756
Run Mode
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
43758
Off Mode
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
43760
Auto Mode
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
43762
Alarm Reset
Int32
N/A
N/A
RW
0 = Disable
1 = Enable