Basler Electric DGC-2020 User Manual

Page 571

background image

9400200990 Rev X

DGC-2020 Modbus

™ Communication

B-139

Holding

Register

Parameter

Range

Read/Write

Supported

Data

Format

Units

40187

Threshold

40-100

R W

DegF

40188

Minimum

40

R -

DegF

40189

Maximum

100

R -

DegF

40190

Stepsize

1

R -

DegF

BATTERY OVERVOLTAGE PRE-ALARM

40191

Enable

0-1

R W

0 =Off
1 =On

40192

Threshold

140-160 (12V)

240-320 (24V)

R W

.1 VoltDC

40193

Minimum

140 / 240

R -

.1 VoltDC

40194

Maximum

160 / 320

R -

.1 VoltDC

40195

Stepsize

1

R -

.1 VoltDC

MAINTENANCE INTERVAL PRE-ALARM

40196

Enable

0-1

R W

0 =Off
1 =On

40197

Threshold

0-5000

R W

Hours

40198

Minimum

0

R -

Hours

40199

Maximum

5000

R -

Hours

40200

Stepsize

10

R -

Hours

ENGINE KW OVERLOAD PRE-ALARM

40201

Enable

0-1

R W

0 =Off
1 =On

40202

Threshold

95-140

R W

% of Rated

40203

Minimum

95

R -

% of Rated

40204

Maximum

140

R -

% of Rated

40205

Stepsize

1

R -

% of Rated

HIGH COOLANT TEMPERATURE PRE-ALARM

40206

Enable

0-1

R W

0 =Off
1 =On

40207

Threshold

100-280

R W

DegF

40208

Minimum

100

R -

DegF

40209

Maximum

280

R -

DegF

40210

Stepsize

1

R -

DegF

LOW OIL PRESSURE PRE-ALARM

40211

Enable

0-1

R W

0 =Off
1 =On

40212

Threshold

3-100

R W

PSI

40213

Minimum

3

R -

PSI

40214

Maximum

100

R -

PSI

40215

Stepsize

1

R -

PSI

LOW BATTERY VOLTAGE PRE-ALARM

40216

Enable

0-1

R W

0 =Off
1 =On

40217

Threshold

60-120 (12V)
120-240 (24V)

R W

.1 VoltDC

40218

Minimum

60 / 120

R -

.1 VoltDC

40219

Maximum

120 / 240

R -

.1 VoltDC

40220

Stepsize

1 (0.1 VDC)

R -

.1 VoltDC

40221

Pre-alarm Activation Time Delay 1-10

R W

Seconds

40222

Activation Time Delay Minimum 1

R -

Seconds