Basler Electric DGC-2020 User Manual
Page 571
![background image](https://www.manualsdir.com/files/773941/content/doc571.png)
9400200990 Rev X
DGC-2020 Modbus
™ Communication
B-139
Holding
Register
Parameter
Range
Read/Write
Supported
Data
Format
Units
40187
Threshold
40-100
R W
DegF
40188
Minimum
40
R -
DegF
40189
Maximum
100
R -
DegF
40190
Stepsize
1
R -
DegF
BATTERY OVERVOLTAGE PRE-ALARM
40191
Enable
0-1
R W
0 =Off
1 =On
40192
Threshold
140-160 (12V)
240-320 (24V)
R W
.1 VoltDC
40193
Minimum
140 / 240
R -
.1 VoltDC
40194
Maximum
160 / 320
R -
.1 VoltDC
40195
Stepsize
1
R -
.1 VoltDC
MAINTENANCE INTERVAL PRE-ALARM
40196
Enable
0-1
R W
0 =Off
1 =On
40197
Threshold
0-5000
R W
Hours
40198
Minimum
0
R -
Hours
40199
Maximum
5000
R -
Hours
40200
Stepsize
10
R -
Hours
ENGINE KW OVERLOAD PRE-ALARM
40201
Enable
0-1
R W
0 =Off
1 =On
40202
Threshold
95-140
R W
% of Rated
40203
Minimum
95
R -
% of Rated
40204
Maximum
140
R -
% of Rated
40205
Stepsize
1
R -
% of Rated
HIGH COOLANT TEMPERATURE PRE-ALARM
40206
Enable
0-1
R W
0 =Off
1 =On
40207
Threshold
100-280
R W
DegF
40208
Minimum
100
R -
DegF
40209
Maximum
280
R -
DegF
40210
Stepsize
1
R -
DegF
LOW OIL PRESSURE PRE-ALARM
40211
Enable
0-1
R W
0 =Off
1 =On
40212
Threshold
3-100
R W
PSI
40213
Minimum
3
R -
PSI
40214
Maximum
100
R -
PSI
40215
Stepsize
1
R -
PSI
LOW BATTERY VOLTAGE PRE-ALARM
40216
Enable
0-1
R W
0 =Off
1 =On
40217
Threshold
60-120 (12V)
120-240 (24V)
R W
.1 VoltDC
40218
Minimum
60 / 120
R -
.1 VoltDC
40219
Maximum
120 / 240
R -
.1 VoltDC
40220
Stepsize
1 (0.1 VDC)
R -
.1 VoltDC
40221
Pre-alarm Activation Time Delay 1-10
R W
Seconds
40222
Activation Time Delay Minimum 1
R -
Seconds