Bias control settings – Basler Electric DGC-2020 User Manual
Page 441

9400200990 Rev X
DGC-2020 Modbus
™ Communication
B-9
Register
Description
Type
Units
Scaling
Factor
R/W
Range
42064
Sync Speed Gain
Float
N/A
N/A
RW
0.001 - 1000
42066
Sync Voltage Gain
Float
N/A
N/A
RW
0.001 - 1000
42068
Max Parallel Time
Int32
Second
Deci
RW
1 - 100000
42070
Mains Fail Transfer Type
Int32
N/A
N/A
RW
0 = Open
1 = Close
42072
In Phase Monitor Enable
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
42074
Dead Gen Close Enable
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
42076
RESERVED
42078
Min Slip Control Limit
Int32
N/A
Centi
RW
0 - 200
42080
Max Slip Control Limit
Int32
N/A
Centi
RW
0 - 200
42082
Rev. Rotation Mains Fail Inhibit
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
42084
Gen Breaker External Status Change Action
Data
Int32
N/A
N/A
RW
0 = Ignore
1 = Follow Always
2 = Follow In Auto
42086
Gen Breaker Fail Output Config Data
Int32
N/A
N/A
RW
0 = Retain
1 = Remove
42088
Mains Fail Mains Breaker Open Config Data
Int32
N/A
N/A
RW
0 = Generator
Start
1 = Generator
Stable
42090
Mains Fail Allow Transfer To Mains In Alarm
State Data
Int32
N/A
N/A
RW
1 = Enable
2 = Disable
42092
Mains Breaker External Status Change
Action Data
Int32
N/A
N/A
RW
0 = Ignore
1 = Follow Always
2 = Follow In Auto
42094
Mains Breaker Fail Output
Int32
N/A
N/A
RW
0 = Retain
1 = Remove
42096
Gen Breaker Transition Delay Data
Int32
Centisecond
Centi
RW
0 - 1000
42098
Mains Breaker Transition Delay Data
Int32
Centisecond
Centi
RW
0 - 1000
42100
Mains Breaker Open Attempts Data
Int32
N/A
N/A
RW
1 - 20
42102
Mains Breaker Close Attempts Data
Int32
N/A
N/A
RW
1 - 20
42104
Mains Breaker Retry Delay Data
Int32
Second
N/A
RW
0 - 1200
42106
Gen Breaker Open Attempts Data
Int32
N/A
N/A
RW
1 - 20
42108
Gen Breaker Close Attempts Data
Int32
N/A
N/A
RW
1 - 20
42110
Gen Breaker Retry Delay Data
Int32
Second
N/A
RW
10 - 3700
42112
Open Transition Delay Data
Int32
Decisecond
Deci
RW
0 - 36000
42114
Max Return Time Data
Int32
Second
N/A
RW
10 - 3700
42116-
248
FUTURE USE
Bias Control Settings
Register
Description
Type
Units
Scaling
Factor
R/W
Range
42250
AVR Kp Proportional Gain
Float
N/A
N/A
RW
0 - 1000
42252
AVR Ki Integral Gain
Float
N/A
N/A
RW
0 - 1000
42254
AVR Kd Derivative Gain
Float
N/A
N/A
RW
0 - 1000
42256
AVR Td Filter Constant
Float
N/A
N/A
RW
0 - 1
42258
AVR Kg Loop Gain
Float
N/A
N/A
RW
0 - 1000
42260
AVR Windup Limit
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
42262
AVR Integrator Limit Plus
Float
N/A
N/A
RW
0 - 1000
42264
AVR Integrator Limit Minus
Float
N/A
N/A
RW
(-1000) - 0
42266
AVR Output Upper Limit
Float
N/A
N/A
RW
0 - 1000
42268
AVR Output Lower Limit
Float
N/A
N/A
RW
(-1000) - 0
42270
RESERVED
42272
Governor Kp Proportional Gain
Float
N/A
N/A
RW
0 - 1000
42274
Governor Ki Integral Gain
Float
N/A
N/A
RW
0 - 1000
42276
Governor Kd Derivative Gain
Float
N/A
N/A
RW
0 - 1000