beautypg.com

General information, Features, Specifications – Basler Electric DGC-2020 User Manual

Page 387: Operating power, Contact inputs, Contact outputs, Section 10, Cem-2020 (contact expansion module) -1, General information -1, Features -1

background image

SECTION 10

• CEM-2020 (CONTACT EXPANSION

MODULE)

General Information

The optional CEM-2020 is a remote auxiliary device that provides additional DGC-2020 contact inputs
and outputs. Two types of modules are available. A low current module (CEM-2020) provides 24 contact
outputs and a high current module (CEM-2020H) provides 18 contact outputs.

Features

CEM-2020s have the following features:

10 Contact Inputs

18 Contact Outputs (CEM-2020H) or 24 Contact Outputs (CEM-2020)

Functionality of Inputs and Outputs assigned by BESTlogicPlus programmable logic

Communications via CAN bus

Specifications

Operating Power

Nominal ...................................... 12 or 24 Vdc
Range ........................................ 8 to 32 Vdc (Withstands cranking ride-through down to 6 Vdc

for 500 ms)

Maximum Consumption

CEM-2020 ........................... 14 W

CEM-2020H ........................ 8 W

Contact Inputs

The CEM-2020 contains 10 programmable inputs that accept dry contacts.

Time from a CEM-2020 input application to:

Shutdown the generator via an alarm = 700 ms max

Close a relay on board the DGC-2020 = 300 ms max

Close a relay on board the CEM-2020 = 550 ms max

NOTES

A CEM-2020 contact input is true (on) if the input is connected to battery
ground with a resistance of less than 200 ohms.

The maximum length of wire that can be accommodated depends on the
resistance of the wire, and the resistance of the contacts of the device driving
the input at the far end of the wire.

The maximum wire length can be calculated as follows:

L

max

= (200

– R

device

)/(Resistance per Foot of Desired Wire)

Contact Outputs

Ratings

CEM-2020

Outputs 13 through 24 .. 1 Adc at 30 Vdc, Form C, gold contacts

Outputs 25 through 36 .. 4 Adc at 30 Vdc, Form C

CEM-2020H

Outputs 13 through 24 .. 2 Adc at 30 Vdc, Form C, gold contacts

Outputs 25 through 30 .. 10 Adc at 30 Vdc, Form C

9400200990 Rev X

DGC-2020 CEM-2020 (Contact Expansion Module)

10-1

This manual is related to the following products: