Figure 4-63. bus condition detection -78 – Basler Electric DGC-2020 User Manual
Page 188
Figure 4-63. Bus Condition Detection
A
Dead Gen Threshold: Adjustable from 0 to 4,800 Vac in 1 Vac increments.
B
Dead Gen Activation Delay: Adjustable from 0.1 to 600 s in 0.1 second increments.
C
Gen Stable Overvoltage Pickup and Dropout: Adjustable from 10 to 99,999 Vac in 1 Vac increments.
D
Gen Stable Undervoltage Pickup and Dropout: Adjustable from 10 to 99,999 Vac in 1 Vac increments.
E
Gen Stable Overfrequency Pickup and Dropout: Adjustable from 46 to 64 Hz in 0.05 Hz increments for
50/60 Hz generator frequency (style number x1xxxxxxx).
F
Gen Stable Underfrequency Pickup and Dropout: Adjustable from 46 to 64 Hz in 0.05 Hz increments for
50/60 Hz generator frequency (style number x1xxxxxxx).
G
Gen Stable Activation Delay: Adjustable from 0.1 to 600 s in 0.1 s increments.
H
Gen Failed Activation Delay: Adjustable from 0.1 to 600 s in 0.1 s increments.
I
Low Line Scale Factor: Adjustable from 0.001 to 3 in increments of 0.001.
J
Alternate Frequency Scale Factor: 0.001 to 100 in increments of 0.001.
K
Dead Gen Threshold (Per Unit): Range varies based on the values of the native unit setting and the
associated rated data parameter.
L
Dead Bus Threshold: Adjustable from 0 to 4,800 Vac in 1 Vac increments.
M
Dead Bus Activation Delay: Adjustable from 0.1 to 600 s in 0.1 s increments.
N
Bus Stable Overvoltage Pickup and Dropout: Adjustable from 10 to 99,999 Vac in 1 Vac increments.
O
Bus Stable Undervoltage Pickup and Dropout: Adjustable from 10 to 99,999 Vac in 1 Vac increments.
P
Bus Stable Overfrequency Pickup and Dropout: Adjustable from 46 to 64 Hz in 0.05 Hz increments for
50/60 Hz generator frequency (style number x1xxxxxxx).
4-78
DGC-2020 BESTCOMSPlus
® Software
9400200990 Rev X