Figure 4-63. Bus Condition Detection

A

Dead Gen Threshold: Adjustable from 0 to 4,800 Vac in 1 Vac increments.

B

Dead Gen Activation Delay: Adjustable from 0.1 to 600 s in 0.1 second increments.

C

Gen Stable Overvoltage Pickup and Dropout: Adjustable from 10 to 99,999 Vac in 1 Vac increments.

D

Gen Stable Undervoltage Pickup and Dropout: Adjustable from 10 to 99,999 Vac in 1 Vac increments.

E

Gen Stable Overfrequency Pickup and Dropout: Adjustable from 46 to 64 Hz in 0.05 Hz increments for

50/60 Hz generator frequency (style number x1xxxxxxx).

F

Gen Stable Underfrequency Pickup and Dropout: Adjustable from 46 to 64 Hz in 0.05 Hz increments for

50/60 Hz generator frequency (style number x1xxxxxxx).

G

Gen Stable Activation Delay: Adjustable from 0.1 to 600 s in 0.1 s increments.

H

Gen Failed Activation Delay: Adjustable from 0.1 to 600 s in 0.1 s increments.

I

Low Line Scale Factor: Adjustable from 0.001 to 3 in increments of 0.001.

J

Alternate Frequency Scale Factor: 0.001 to 100 in increments of 0.001.

K

Dead Gen Threshold (Per Unit): Range varies based on the values of the native unit setting and the

associated rated data parameter.

L

Dead Bus Threshold: Adjustable from 0 to 4,800 Vac in 1 Vac increments.

M

Dead Bus Activation Delay: Adjustable from 0.1 to 600 s in 0.1 s increments.

N

Bus Stable Overvoltage Pickup and Dropout: Adjustable from 10 to 99,999 Vac in 1 Vac increments.

O

Bus Stable Undervoltage Pickup and Dropout: Adjustable from 10 to 99,999 Vac in 1 Vac increments.

P

Bus Stable Overfrequency Pickup and Dropout: Adjustable from 46 to 64 Hz in 0.05 Hz increments for

50/60 Hz generator frequency (style number x1xxxxxxx).