Basler Electric DGC-2020 User Manual
Page 233

Name
Description
Symbol
Status Input
Front Panel
Buttons
True while the UP front panel button is pressed.
Status Input
Fuel Leak
True when the Fuel Leak Detect input is true.
Status Input
Generator
Breaker Status
True when the generator breaker is closed.
Status Input
Generator Dead
True when the Gen Dead condition settings have
been exceeded.
Status Input
Generator Fail
True when the Gen Fail condition settings have been
exceeded.
Status Input
Gen Forward
Rotation
True when the sensed generator phase rotation
matches the generator phase rotation specified in the
system settings.
Status Input
Gen Reverse
Rotation
True when the sensed generator phase rotation
differs from the generator phase rotation specified in
the system settings.
Status Input
Generator Stable
True when the Gen Stable condition settings have
been exceeded.
Status Input
Generator
Protection
True when the 27-1 element is tripped.
Status Input
Generator
Protection
True when the 27-2 element is tripped.
Status Input
Generator
Protection
True when the 59-1 element is tripped.
Status Input
Generator
Protection
True when the 59-2 element is tripped.
Status Input
Generator
Protection
True when the 32 element is tripped.
Status Input
Generator
Protection
True when the 40 element is tripped.
Status Input
Generator
Protection
True when the 47 element is tripped.
Status Input
Generator
Protection
True when the 51-1 element is tripped.
Status Input
Generator
Protection
True when the 51-2 element is tripped.
9400200990 Rev X
DGC-2020 BESTlogic
™
Plus Programmable Logic
5-5