Basler Electric DGC-2020 User Manual

Page 233

background image

Name

Description

Symbol

Status Input

Front Panel
Buttons

True while the UP front panel button is pressed.

Status Input

Fuel Leak

True when the Fuel Leak Detect input is true.

Status Input

Generator
Breaker Status

True when the generator breaker is closed.

Status Input

Generator Dead

True when the Gen Dead condition settings have
been exceeded.

Status Input

Generator Fail

True when the Gen Fail condition settings have been
exceeded.

Status Input

Gen Forward
Rotation

True when the sensed generator phase rotation
matches the generator phase rotation specified in the
system settings.

Status Input

Gen Reverse
Rotation

True when the sensed generator phase rotation
differs from the generator phase rotation specified in
the system settings.

Status Input

Generator Stable

True when the Gen Stable condition settings have
been exceeded.

Status Input

Generator
Protection

True when the 27-1 element is tripped.

Status Input

Generator
Protection

True when the 27-2 element is tripped.

Status Input

Generator
Protection

True when the 59-1 element is tripped.

Status Input

Generator
Protection

True when the 59-2 element is tripped.

Status Input

Generator
Protection

True when the 32 element is tripped.

Status Input

Generator
Protection

True when the 40 element is tripped.

Status Input

Generator
Protection

True when the 47 element is tripped.

Status Input

Generator
Protection

True when the 51-1 element is tripped.

Status Input

Generator
Protection

True when the 51-2 element is tripped.

9400200990 Rev X

DGC-2020 BESTlogic

Plus Programmable Logic

5-5