4 proportional directional control valve type mpye, Proportional directional control valve type mpye – Festo Кабели и принадлежности User Manual

Page 86

background image

3. Installation

3−8

Festo P.BE−SPC200−EN en 0901d

3.2.4

Proportional directional control valve type MPYE−...

·

Fit the proportional directional control valve as close as
possible to the drive. Short compressed air tubing will
ensure the dynamics of the system.

·

If the proportional directional control valve is to be used
in an environment subjected to heavy electrical interferĆ
ence, it should be insulated from the mounting surface.

·

Fitting onto moving parts
If fitted to moving parts, the proportional directional conĆ
trol valve must be mounted at right−angles to the direcĆ
tion of movement. Acceleration forces then have no influĆ
ence on the valve slide setting.

1

2

3

1

Fitting at right angles to the direction of movement

2

Not permitted

3

Proportional directional control valve type MPYE−...

Fig. 3/1:

Fitting to moving parts

·

Use silencers with a large rated flow (e.g. U−1/8).

Reducing loud exhaust noises:

·

Install larger silencers with the aid of tubing or pass the
ducted exhaust into a small compressed air reservoir and
exhaust this with a large silencer. Make sure that the
screw connectors and tubing provide sufficient flow. Keep
the tubing as short as possible.