8. Diagnosis and error treatment
8−18
Festo P.BE−SPC200−EN en 0901d
Fault class 4:
Hardware fault in the operating phase
Fault
stage
Eliminating faults
Operating status / fault explanation
Fault
message
B
00006x04
Load voltage for field devices and proporĆ
tional directional control valve is too low.
·
Eliminate undervoltage on
the operating voltage conĆ
nection (X2).
C
zzz07x04
Fault in monitoring the field bus module
(PROFIBUS, Interbus, DeviceNet, etc.); field
bus module cannot be addressed. Location
in the basic unit or field bus module defecĆ
tive or field bus module not fully inserted.
zzz = fault time point
001: Fault in initialization phase
000: Fault in the operating phase
·
Make sure that the field bus
module is fully inserted.
·
Check location; if necessary
select different location
·
Switch system off/on again
If this fault occurs again, return
for servicing
zzz08x04
Fault on analogue input module
zzz = channel number and fault number
Ĉ Channel number 1 ... 4):
1
1z: analogue channel 1,
1
2z: analogue channel 2 etc.
Ĉ Fault number (1 ... 3):
1z
1: timeout when reading the analogue
value from channel z
1z
2: upper software end position violated
when reading from channel z
1z
3: lower software end position violated
when reading from channel z
·
Replace analogue input
module
·
Adapt voltage range to
defined positioning range
D
zzz09x04
Fault on the V.24 interface (X4);
zzz = fault type
001: Overrun
002: Parity fault
·
Check diagnostic module or
connecting cable; if necessĆ
ary set lower baud rate
zzz0Ax04
Fault on the V.24 interface for the control
panel (X3)
zzz = fault type
001: Overrun
002: Parity fault
·
Check diagnostic module
and control panel or connecĆ
tion
zzz = Additional information
yy = Fault number
x
= Axis identifier (0 = fault is not axis−related)