beautypg.com

Festo Кабели и принадлежности User Manual

Page 374

background image

8. Diagnosis and error treatment

8−18

Festo P.BE−SPC200−EN en 0901d

Fault class 4:

Hardware fault in the operating phase

Fault
stage

Eliminating faults

Operating status / fault explanation

Fault
message

B

00006x04

Load voltage for field devices and proporĆ
tional directional control valve is too low.

·

Eliminate undervoltage on
the operating voltage conĆ
nection (X2).

C

zzz07x04

Fault in monitoring the field bus module
(PROFIBUS, Interbus, DeviceNet, etc.); field
bus module cannot be addressed. Location
in the basic unit or field bus module defecĆ
tive or field bus module not fully inserted.
zzz = fault time point
001: Fault in initialization phase
000: Fault in the operating phase

·

Make sure that the field bus
module is fully inserted.

·

Check location; if necessary
select different location

·

Switch system off/on again

If this fault occurs again, return
for servicing

zzz08x04

Fault on analogue input module
zzz = channel number and fault number
Ĉ Channel number 1 ... 4):

1

1z: analogue channel 1,

1

2z: analogue channel 2 etc.

Ĉ Fault number (1 ... 3):

1z

1: timeout when reading the analogue

value from channel z

1z

2: upper software end position violated

when reading from channel z

1z

3: lower software end position violated

when reading from channel z

·

Replace analogue input
module

·

Adapt voltage range to
defined positioning range

D

zzz09x04

Fault on the V.24 interface (X4);
zzz = fault type
001: Overrun
002: Parity fault

·

Check diagnostic module or
connecting cable; if necessĆ
ary set lower baud rate

zzz0Ax04

Fault on the V.24 interface for the control
panel (X3)
zzz = fault type
001: Overrun
002: Parity fault

·

Check diagnostic module
and control panel or connecĆ
tion

zzz = Additional information
yy = Fault number
x

= Axis identifier (0 = fault is not axis−related)