2 addressing the control signals, Addressing the control signals – Festo Кабели и принадлежности User Manual
Page 282
7. Description of the commands
7−16
Festo P.BE−SPC200−EN en 0901d
7.2.2
Addressing the control signals
Record Select mode
Control sigĆ
nal
I/O module
addresses
Address with
fieldbus
Description
ENABLE
I0.9
I10.0
Controller enable (1 = controller enabled)
RESET
I0.8
I10.1
Reset programs (in conjunction with
STOP=0)
STOP
I0.7
I10.2
Stop positioning task (0 = stopped)
CLK_A/B
I0.6 / I0.5
I10.3 / I10.4
Start NC record from program A/B
RECBIT1...5
I0.0 ... I0.4
ć
Bits for NC record number: RECBIT1 for2^0
etc. (record bit)
RECBIT...
ć
I11.0 ... I11.15
RECBIT... with control via a field bus module
as 2−byte value from 0 to 999, see manual
on the field bus module.
READY
Q0.7
Q10.0
System ready to operate
ACK_A/B
Q0.6 / Q0.5
Q10.1 / Q10.2
Task accepted for program A/B (acknowlĆ
edge)
RC_A/B
Q0.4 / Q0.3
Q10.3 / Q10.4
NC record concluded by program A/B (reĆ
cord complete)