B. Optimizing the positioning behaviour
B−13
Festo P.BE−SPC200−EN en 0901d
Effect
Cause
Remedy
Stability problem, very frequent swinging around the nominal position
1
2
3
Ĉ Incorrect mass load confiĆ
gured or programmed (M37)
Ĉ Gain factor set too high
Ĉ Damping factor set too low
Ĉ Signal filter factor set too
high (smooth acceleration/
speed signal but continuous
swinging)
Ĉ Or very noisy acceleration
signal with high amplitude
Ĉ Minimum mass load not
reached
Ĉ Too small tolerance
demanded
·
Correct configuration or
program
·
Correct parameters
·
Correct parameters
·
Reduce signal filter factor
·
Increase signal filter factor
·
Increase basic load
(see chapter 3.2.9)
·
Increase tolerance
1
Nominal position
2
Actual position
3
Speed