C. Technical appendix

C−17

Festo P.BE−SPC200−EN en 0901d

Formula for maximum cable length:

L

v

NJ

ǒ

V

Bmin

* V

OUT

ńVALmin

Ǔ

@ A @ Ë

CU

Nj

{2

@ I

2

) I

1

}

Meaning

·

V

OUT/VALmin

w

22.8 V

·

V

Bmin

= minimum operating voltage supply

(on the power unit)

·

Current I

1

= current for electronics etc. (24 V)

·

Current I

2

= current for outputs, field devices and

proportional directional control valves etc.
(24 L)

·

A = cross−sectional area (uniform e.g. 1.5 mm

2

)

·

κ

= conductance value of the cables

(uniform e.g.

κ

CU

= 56

m

mm

2

@

)

ġ

Example:
SPC200−CPU4 with basic components and field devices for
2Ăaxes:

I1

= 1 A

I2

= 2.3 A

V

Bmin

= 24 V

V

OUT/VALmin

= 22.8 V

κ

CU

= 56

m

mm

2

@ ġ

Result:
L

≤ 18 m for A = 1.5 mm

2

L

≤ 9 m for A = 0.75 mm

2