Festo Кабели и принадлежности User Manual
Page 463
C. Technical appendix
C−17
Festo P.BE−SPC200−EN en 0901d
Formula for maximum cable length:
L
v
NJ
ǒ
V
Bmin
* V
OUT
ńVALmin
Ǔ
@ A @ Ë
CU
Nj
{2
@ I
2
) I
1
}
Meaning
·
V
OUT/VALmin
w
22.8 V
·
V
Bmin
= minimum operating voltage supply
(on the power unit)
·
Current I
1
= current for electronics etc. (24 V)
·
Current I
2
= current for outputs, field devices and
proportional directional control valves etc.
(24 L)
·
A = cross−sectional area (uniform e.g. 1.5 mm
2
)
·
κ
= conductance value of the cables
(uniform e.g.
κ
CU
= 56
m
mm
2
@
)
ġ
Example:
SPC200−CPU4 with basic components and field devices for
2Ăaxes:
I1
= 1 A
I2
= 2.3 A
V
Bmin
= 24 V
V
OUT/VALmin
= 22.8 V
κ
CU
= 56
m
mm
2
@ ġ
Result:
L
≤ 18 m for A = 1.5 mm
2
L
≤ 9 m for A = 0.75 mm
2
This manual is related to the following products: