3−34

Festo P.BE−SPC200−EN en 0901d

Connecting cable type KSPC−AIF−... is supplied already fitted
with a 5−pin screw terminal.

Caution
The axis interface connection is not protected against inĆ
correct polarity. Make sure that the assignment is correct,
e.g. when you fit the screw terminal yourself after shortenĆ
ing the cable.

1

Earth/ground
connection

2

Pin assignment:
1: CAN−LOW

(brown)

2: CAN−HIGH

(white)

3: 24 V (yellow)
4: 0 V (green)
5: 24 V load

voltage (grey)

1

2
3

4
5

1

2

Fig. 3/10: Pin assignment of the plug for the first axis interface string (X1)

Follow the installation instructions supplied with the cable
when connecting the cable screening.

Depending on the cable used, connect the cable screening
either to the earth connection

1 or to a large surface, comĆ

plying with EMC requirements as follows:

ć

to a screening plate intended for this purpose

ć

through the cable opening into the control cabinet.