8. Diagnosis and error treatment
8−19
Festo P.BE−SPC200−EN en 0901d
Fault class 4:
Hardware fault in the operating phase
Fault
stage
Eliminating faults
Operating status / fault explanation
Fault
message
C
zzz0Bx04
zzz0Cx04
Fault on:
Ĉ Third I/O module (B)
Ĉ Fourth I/O module (C)
(zzz as with fault class 4,
fault numbers 4 and 5)
·
Eliminate undervoltage or
short circuit
1)
zzz0Dx04
Fault on subcontroller module
(second AIF string)
·
Insert module fully or
replace
zzz0Ex04
Fault on stepping motor module
zzz = fault type:
001: Stepping motor controller not ready
002: No reference travel carried out
003: Positive limit switch activated
004: Negative limit switch activated
005: Reference travel interrupted
008: Both limit switches active
·
Check voltage supply at
signal connector (X31) of the
stepping motor module.
·
Check stepping motor conĆ
troller or connecting cable
·
Carry out reference travel
·
Bring drive out of end posiĆ
tion and carry out reference
travel
·
Bring drive out of end posiĆ
tion and carry out reference
travel
·
Carry out reference travel
again
·
Check limit switches
zzz0Fx04
Reserved
ć
zzz10004
Configured assignment of a local I/O range to
the specified field bus I/O range in the
SPC200 is not permissible because the local
module itself is not present.
zzz = I/O word no.:
000: Assignment to IW11 faulty
001: Assignment to IW12 faulty
002: Assignment to IW13 faulty
003: Assignment to QW11 faulty
004: Assignment to QW12 faulty
005: Assignment to QW13 faulty
·
Correct the configuration;
see description of the field
bus module or the configurĆ
ation menu of WinPISA from
version 4.41.