beautypg.com

Festo Кабели и принадлежности User Manual

Page 375

background image

8. Diagnosis and error treatment

8−19

Festo P.BE−SPC200−EN en 0901d

Fault class 4:

Hardware fault in the operating phase

Fault
stage

Eliminating faults

Operating status / fault explanation

Fault
message

C

zzz0Bx04
zzz0Cx04

Fault on:
Ĉ Third I/O module (B)
Ĉ Fourth I/O module (C)
(zzz as with fault class 4,
fault numbers 4 and 5)

·

Eliminate undervoltage or
short circuit

1)

zzz0Dx04

Fault on subcontroller module
(second AIF string)

·

Insert module fully or
replace

zzz0Ex04

Fault on stepping motor module
zzz = fault type:
001: Stepping motor controller not ready

002: No reference travel carried out
003: Positive limit switch activated

004: Negative limit switch activated

005: Reference travel interrupted

008: Both limit switches active

·

Check voltage supply at
signal connector (X31) of the
stepping motor module.

·

Check stepping motor conĆ
troller or connecting cable

·

Carry out reference travel

·

Bring drive out of end posiĆ
tion and carry out reference
travel

·

Bring drive out of end posiĆ
tion and carry out reference
travel

·

Carry out reference travel
again

·

Check limit switches

zzz0Fx04

Reserved

ć

zzz10004

Configured assignment of a local I/O range to
the specified field bus I/O range in the
SPC200 is not permissible because the local
module itself is not present.
zzz = I/O word no.:
000: Assignment to IW11 faulty
001: Assignment to IW12 faulty
002: Assignment to IW13 faulty
003: Assignment to QW11 faulty
004: Assignment to QW12 faulty
005: Assignment to QW13 faulty

·

Correct the configuration;
see description of the field
bus module or the configurĆ
ation menu of WinPISA from
version 4.41.