8. Diagnosis and error treatment

8−25

Festo P.BE−SPC200−EN en 0901d

Fault class 6:

Fault in positioning task or identification travel

Fault
stage

Eliminating faults

Operating status / fault explanation

Fault
message

C

nnn06x06

NC command G00 is not possible as a
dynamic identification travel has not been
carried out

·

Carry out dynamic identificaĆ
tion travel

nnn07x06

The controller in the SPC200 cannot be
initialized

·

Check controller, axis and
application data

nnn08x06

A task for this axis is already active (positionĆ
ing, identification ...). A new task can only be
accepted when the old task is concluded.

·

Correct the NC record or stop
the system before carrying
out the activity

nnn09x06

Contents of a position register are not valid

·

Correct NC record

nnn0Ax06 Violation of stroke limit value (M40) with

M39

·

Check stroke limit value and
variable value with comĆ
mand M39; if necessary
correct NC record

0000Bx06 System identification aborted as enable

signal is missing

·

Set ENABLE input and start
identification travel again

B

0000Cx06

Reserved

ć

0000Dx06 Reserved

ć

C

0000Ex06

Identification data not valid

·

Carry out system identificaĆ
tion again

nnn0Fx06

Non−permitted positioning quality class

·

Correct NC record

zzz = Additional information
yy = Fault number
x

= Axis identifier (0 = fault is not axis−related)

nnn = NC record number of the accessing NC command