8. Diagnosis and error treatment
8−25
Festo P.BE−SPC200−EN en 0901d
Fault class 6:
Fault in positioning task or identification travel
Fault
stage
Eliminating faults
Operating status / fault explanation
Fault
message
C
nnn06x06
NC command G00 is not possible as a
dynamic identification travel has not been
carried out
·
Carry out dynamic identificaĆ
tion travel
nnn07x06
The controller in the SPC200 cannot be
initialized
·
Check controller, axis and
application data
nnn08x06
A task for this axis is already active (positionĆ
ing, identification ...). A new task can only be
accepted when the old task is concluded.
·
Correct the NC record or stop
the system before carrying
out the activity
nnn09x06
Contents of a position register are not valid
·
Correct NC record
nnn0Ax06 Violation of stroke limit value (M40) with
M39
·
Check stroke limit value and
variable value with comĆ
mand M39; if necessary
correct NC record
0000Bx06 System identification aborted as enable
signal is missing
·
Set ENABLE input and start
identification travel again
B
0000Cx06
Reserved
ć
0000Dx06 Reserved
ć
C
0000Ex06
Identification data not valid
·
Carry out system identificaĆ
tion again
nnn0Fx06
Non−permitted positioning quality class
·
Correct NC record
zzz = Additional information
yy = Fault number
x
= Axis identifier (0 = fault is not axis−related)
nnn = NC record number of the accessing NC command