8. Diagnosis and error treatment

8−6

Festo P.BE−SPC200−EN en 0901d

LED on the axis interface

Reaction

Sequence

Operating status

Eliminating faults

POWER LED

ON

OFF

Operating voltage applied

None

ON

OFF

Operating voltage not applied

Check operating voltage connecĆ
tion and load voltage connection
on the SPC200 (pin 1 and pin 2).

ERROR LED

ON

OFF

Ĉ Switch−on phase (3...4 seconds)

or

Ĉ Hardware fault, SPC200 is not

ready for communication

·

None

·

Servicing required

ON

OFF

Ĉ No internal fault registered

None

ON

OFF

Lights up briefly once when the
device is switched on

None

Flashes at 1 second intervals:
Ĉ Once (fault no. 1)

Axis interface not initialized

Ĉ Twice (fault no. 2)

A CAN−module on the bus is in
the OFF status

Ĉ Three times (fault no. 3)

Incorrect type ID read

Ĉ Four times

Emergency stop activated

Ĉ Five times

Linear potentiometer is in end
position or is not connected;
cable between axis interface and
measuring system defective;
measuring head (DNCI) not conĆ
nected to axis interface.

Ĉ Six times

Timeout

Ĉ Seven times

Load voltage too low

·

Switch system on again, or
replace defective axis interface

·

Switch system on again, or
replace defective CP module

·

Remove non−permitted
module or servicing required

·

None

·

Bring linear potentiometer out
of the end position or connect;
DNCI: Install measuring head
and connect to axis interface;
for correct fitting see operatĆ
ing instructions for the DNCI

·

Check SPC200 and AIF cable,
if there are faults see section
8.2, or servicing required

·

Check load voltage