8. Diagnosis and error treatment

8−33

Festo P.BE−SPC200−EN en 0901d

8.3

Eliminating faults in the system

8.3.1

Faults when switching on

1) No display on the SPC200

Cause

Remedy

Remarks

Supply voltage is not correct
or SPC 200 is defective

Check supply voltage or
servicing required

See section 3.2.1

2) Axis makes small movements backwards and

forwards

Cause

Remedy

Remarks

Axis or application data not
correct

Check axis or application data

See section 6.2

System identification has not
been carried out

Carry out system identification

See section 6.8

System is not earthed
correctly

Check earthing measures

See section 3.5

Measuring system or measurĆ
ing system cable is defective

Check measuring system and

measuring system cable and

replace if necessary

Check by shifting manually or
carry out movement test,
see section 4.4.2