8. Diagnosis and error treatment
8−16
Festo P.BE−SPC200−EN en 0901d
Fault class 4:
Hardware fault in the operating phase
Fault
stage
Fault
message
Operating status / fault explanation
Eliminating faults
C
zzz01x04
Internal system fault (Watchdog fault)
zzz = Fault type (see following description)
·
Switch system off/on again;
·
Check level and stability of
power supply
If this fault occurs again, return
for servicing
001: Fault in the switch−off phase; when the
system was switched off, certain sysĆ
tem functions (Power Down functions)
were not carried out. perhaps the
power supply module is defective
·
If necessary replace power
supply module
002: Fault whilst monitoring the power supĆ
ply during operation; unstable power
supply or environment subjected to
strong interference; or the power supĆ
ply module is defective.
·
If necessary replace power
supply module
·
If necessary eliminate interĆ
ference
003/004: Fault in monitoring the memory
range of the firmware (memory protecĆ
tion violation); environment subjected
to strong interference or basic unit is
defective.
·
Carry out Data Reset
·
If necessary eliminate interĆ
ference
·
If necessary replace basic
unit
005: Fault in monitoring the memory range
of the user programs (memory protecĆ
tion violation); environment subjected
to strong interference or basic unit is
defective.
·
Carry out Data Reset
·
If necessary eliminate interĆ
ference
·
If necessary replace basic
unit
006: Fault in accessing adaptation data The
data have not been initialized.
·
Carry out Data Reset.
zzz =
Additional information
yy =
Fault number
x
=
Axis identifier (0 = fault is not axis−related)