4. Commissioning

4−14

Festo P.BE−SPC200−EN en 0901d

STOP input

You can stop the processing of the current NC record via the
STOP input. If a positioning task is running at that moment, it
will be interrupted. The current positions become the nomĆ
inal positions (closed−loop controlled stop).

The stop status is cancelled by:

1. a 1−signal at the STOP input.

2. renewed start of the sequence, e.g. by a rising edge at

the START input.

START input

Using the start input, you can start the selected starting proĆ
gram, or resume the current program after a stop, or set the
current program back to the initial state, or acknowledge a
fault message; for details see chapter 5.

The START input is edge−triggered, and responds exclusively
to the level change from 0−signal to 1−signal.

READY output

This output supplies a 1−signal if the system is ready to operĆ
ate. A 0−signal at this output indicates that the SPC200 is not
yet ready to operate, because:

ć

there is a system fault or positioning fault

ć

the enable signal is missing or

ć

the rising signal edge required at the ENABLE input for
the first commissioning, after a Data Reset or after the
movement test, is missing (e.g. the ENABLE input is incorĆ
rectly connected to the supply voltage).