beautypg.com

5 controller data, Controller data, Stop behaviour – Festo Кабели и принадлежности User Manual

Page 166

background image

4. Commissioning

4−22

Festo P.BE−SPC200−EN en 0901d

4.3.5

Controller data

The controller data are optional parameters, and are valid
only for a pneumatic axis, see appendix B.
It is advisable to alter these parameters only in small steps
(0.1 ... 0.3), and to depict the changes in the movement seĆ
quence graphically using the function Represent measured
values" (WinPISA).

Exception: the Positioning timeout parameter
The Positioning timeout is used to monitor the time duration
of a positioning task. If the configured time after the beginĆ
ning of a positioning task elapses without an MC signal being
set, the SPC200 generates a fault. The parameter value 0
switches off the function.

Controller data

Unit

Default values

Example

Gain factor

ć

1

1

Damping factor

ć

1

1

Signal filter factor

ć

1

1

Positioning timeout

s

2

0

Stop behaviour

Stop behaviour can be configured starting with firmware verĆ
sion 4.93 in combination with WinPISA as from 4.51:

ć

The position at the time of the stop signal becomes the
setpoint position (default). After standstill, the axis runs
back to this position.

ć

The current position at standstill becomes the setpoint
position.
This function is only available as from firmware version
4.93 and can be configured with WinPISA as from version
4.51.

New feature
as from

OS 4.93