8. Diagnosis and error treatment
8−22
Festo P.BE−SPC200−EN en 0901d
Fault class 5:
Sequence control fault
Fault
stage
Eliminating faults
Operating status / fault explanation
Fault
message
C
0050Cx05
Conversion for this nominal value has
already taken place.
·
Analogue nominal value
input must be deactivated
with M12, before it is actiĆ
vated again with M10.
zzz0Dx05
Reserved
ć
zzz0Ex05
The programmed nominal value input does
not exist.
·
Correct NC record
zzz0Fx05
Reserved
zzz10x05
Programmed input or output is not availĆ
able. Input/output address or I/O module
does not exist.
·
Correct NC record.
Correct input/output
address
zzz11x05
Register index is not valid (index > 99)
·
Correct NC record
zzz12x05
The absolute preselection value (G25) in
the selected register @n is not between the
last nominal position or the last switchover
position and the new nominal position.
·
Correct NC record or register
contents.
Please note: If the axis was
stopped by a stop signal during
the movement command and
was then supposed to continue
moving, the current actual
position no longer corresponds
to the original one.
zzz13x05
The nominal value specification via field
bus (M10, channel 5) cannot be activated,
since no field bus card is present or the
field bus card used does not support this
function.
·
Check type and software verĆ
sions of the field bus card,
replace if necessary.
permitted:
ć SPC200−COM−PDP from
version 2.0
ć SPC200−COM−DN2
ć SPC200−COM−CO2
zzz = Additional information
yy = Fault number
x
= Axis identifier (0 = fault is not axis−related)