beautypg.com

Festo Кабели и принадлежности User Manual

Page 378

background image

8. Diagnosis and error treatment

8−22

Festo P.BE−SPC200−EN en 0901d

Fault class 5:

Sequence control fault

Fault
stage

Eliminating faults

Operating status / fault explanation

Fault
message

C

0050Cx05

Conversion for this nominal value has
already taken place.

·

Analogue nominal value
input must be deactivated
with M12, before it is actiĆ
vated again with M10.

zzz0Dx05

Reserved

ć

zzz0Ex05

The programmed nominal value input does
not exist.

·

Correct NC record

zzz0Fx05

Reserved

zzz10x05

Programmed input or output is not availĆ
able. Input/output address or I/O module
does not exist.

·

Correct NC record.
Correct input/output
address

zzz11x05

Register index is not valid (index > 99)

·

Correct NC record

zzz12x05

The absolute preselection value (G25) in
the selected register @n is not between the
last nominal position or the last switchover
position and the new nominal position.

·

Correct NC record or register
contents.

Please note: If the axis was
stopped by a stop signal during
the movement command and
was then supposed to continue
moving, the current actual
position no longer corresponds
to the original one.

zzz13x05

The nominal value specification via field
bus (M10, channel 5) cannot be activated,
since no field bus card is present or the
field bus card used does not support this
function.

·

Check type and software verĆ
sions of the field bus card,
replace if necessary.
permitted:
ć SPC200−COM−PDP from

version 2.0

ć SPC200−COM−DN2
ć SPC200−COM−CO2

zzz = Additional information
yy = Fault number
x

= Axis identifier (0 = fault is not axis−related)