4. Commissioning

4−26

Festo P.BE−SPC200−EN en 0901d

If necessary, you can ascertain the actual configuration reĆ
cognised in the switch−on phase with the command ACTUAL
CONFIG. in the menu CONFIG. SYSTEM (see section 6.2).

4. If the recognised actual configuration does not comply

with your wishes: switch off the power supply and create
the desired configuration.

5. If the recognised actual configuration fulfills your wishes,

press any button in order to quit the fault message. The
basic setting will then be displayed again.

6. Select the command OPERATING MODE in the menu

CONFIG. and press the Enter button.

SET CONFIGUR.

SAVE CONFIGUR. ?

7. Press the Enter button in order to save the actual conĆ

figuration as the nominal configuration.

8. If modifications have been made to the axis configurĆ

ation, you will receive the following message:

RESTORE FACTORY

SETTINGS ?

Please note
This message indicates that all data are reset to the status
as at delivery. All data and programs entered will be lost.

9. Press the ESC button in order to interrupt. Or press the

Enter button in order to delete all the data in the SPC200
and to save the hardware configuration.

When the current hardware configuration is saved, the actual
configuration becomes the nominal configuration. The conĆ
trol panel then shows the basic setting again.