8. Diagnosis and error treatment
8−17
Festo P.BE−SPC200−EN en 0901d
Fault class 4:
Hardware fault in the operating phase
Fault
stage
Eliminating faults
Operating status / fault explanation
Fault
message
B
zzz02x04
AIF string no longer functions
1)
(zzz as with fault class 1, fault number 2)
·
Check and if necessary
replace modules or compoĆ
nents on the AIF string
1)
zzz03x04
Fault in measuring system
z
00: ć Measuring system in the end
position or
ć Measuring system defective or
ć AIF string no longer functions
1)
z
01: Reference position is invalid
0zz: Concerns the 1st AIF string (on the
power supply module
1zz: Concerns the 2nd AIF string (on the
subcontroller module
·
Check module on AIF string
and string assignment or
bring measuring system out
of end position or replace
measuring system cable
1)
·
Replace AIF
·
Repeat reference run
C
zzz04x04
Fault on first I/O module
zzz = short circuit at input (E) or output (A)
or undervoltage:
000: short circuit at E and A and undervolt.
001: short circuit at E and A
002: short circuit at E and A and undervolt.
003: short circuit at E
004: short circuit at A and undervoltage
005: short circuit at A
006: undervoltage
·
Eliminate undervoltage or
short circuit
2)
zzz05x04
Fault on second I/O module
zzz = short circuit at input or output or
undervoltage
000...006: Additional information as with
fault no. zzz04004
·
Eliminate undervoltage or
short circuit
zzz = Additional information, yy = fault number, x = axis identifier (0 = fault is not axis−related)
1)
When this fault has been eliminated and quitted, the system tries at first to commission the axis
interface string. If this is not possible, the axis interface string will be initialized again.
This procedure can take a certain amount of time (max. 10 seconds), depending on the system
configuration used.
2)
If there is a short circuit at the input, the operating voltage must be switched on again.