4. Commissioning
4−38
Festo P.BE−SPC200−EN en 0901d
Possible problems
Cause
Remedy
Remarks
The slide moves into
an end position.
The control direction is
not the same as the
direction of positioning
of the slide.
Swap the connecting
tubing on the
proportional directional
control valve.
See also appendix A
Measuring system or
measuring system cable
is defective.
Replace measuring
system or measuring
system cable
*)
Check first with
MOVEMENT TEST
The slide moves one
position.
The axis or application
data are not correct.
Correct the data
See section 6.2
The control panel
shows a fault number
See section 8.2
Eliminate fault
See section 8.2
The slide does not
move
The valve cable is
defective
Check the cable
*)
See also appendix A
No supply pressure
Switch on the
compressed air supply
or check the tubing.
See also section 3.2
The controller is
switched off because
there is no ENABLE
signal.
Apply a 1−signal to the
ENABLE input.
See also Fig. 4.2
System has stopped.
Apply a 1−signal to the
STOP input.
See also Fig. 4.2
Proportional directional
control valve is defective
Replace the
proportional directional
control valve.
*)
Check first with
MOVEMENT TEST
*)
Check and if necessary replace