beautypg.com

2 fault classes, Fault classes – Festo Кабели и принадлежности User Manual

Page 369

background image

8. Diagnosis and error treatment

8−13

Festo P.BE−SPC200−EN en 0901d

8.2.2

Fault classes

Fault class 0:

No fault

Fault
stage

Fault
message

Operating status / fault explanation

Eliminating faults

ć

00000000 No fault registered

Fault class 1:

Initialization phase Fault in the initialization of
components and modules

Fault
stage

Fault
message

Operating status / fault explanation

Eliminating faults

A

zzz01x01

Internal system fault
zzz = 001, 002: System memory fault;
perhaps the basic unit is defective

Servicing required

·

If the fault occurs
more than once,
replace basic unit

zzz02x01

Faults in initializing the axis interface string
zzz = Fault location and fault type:
Ĉ Fault location:

0zz:

Fault on 1st. AIF string

1zz:

Fault on the 2nd AIF string

Ĉ Type of fault:

z

00:

Active fault could not be acknowledged

z

01, z0B:

Fault on the first measuring system

z

02, z0C:

Fault on the second measuring system

z

03, z09:

Fault on the 1st. AIF

z

04, z0A:

Fault on the 2nd. AIF

z

05:

Fault on the 1st. CP module

z

06:

Fault on the 2nd. CP module

z

07, z08, z0D: Bus error

·

Check and if
necessary replace
modules or comĆ
ponents on the
AIF string

·

Check operating
system version in
SPC200. Is it perĆ
missible for the
axis interfaces
used? (see also
page XVI)

zzz03x01

Defective or non−permitted component
zzz =

Location number, in ascending order from
left to right (000...003 for 4, and
000...005 for 6 locations)

Replace or remove
component

zzz = Additional information
yy = Fault number
x

= Axis identifier (0 = fault is not axis−related)

AIF = Axis interface