8. Diagnosis and error treatment
8−13
Festo P.BE−SPC200−EN en 0901d
8.2.2
Fault classes
Fault class 0:
No fault
Fault
stage
Fault
message
Operating status / fault explanation
Eliminating faults
ć
00000000 No fault registered
Fault class 1:
Initialization phase Fault in the initialization of
components and modules
Fault
stage
Fault
message
Operating status / fault explanation
Eliminating faults
A
zzz01x01
Internal system fault
zzz = 001, 002: System memory fault;
perhaps the basic unit is defective
Servicing required
·
If the fault occurs
more than once,
replace basic unit
zzz02x01
Faults in initializing the axis interface string
zzz = Fault location and fault type:
Ĉ Fault location:
0zz:
Fault on 1st. AIF string
1zz:
Fault on the 2nd AIF string
Ĉ Type of fault:
z
00:
Active fault could not be acknowledged
z
01, z0B:
Fault on the first measuring system
z
02, z0C:
Fault on the second measuring system
z
03, z09:
Fault on the 1st. AIF
z
04, z0A:
Fault on the 2nd. AIF
z
05:
Fault on the 1st. CP module
z
06:
Fault on the 2nd. CP module
z
07, z08, z0D: Bus error
·
Check and if
necessary replace
modules or comĆ
ponents on the
AIF string
·
Check operating
system version in
SPC200. Is it perĆ
missible for the
axis interfaces
used? (see also
page XVI)
zzz03x01
Defective or non−permitted component
zzz =
Location number, in ascending order from
left to right (000...003 for 4, and
000...005 for 6 locations)
Replace or remove
component
zzz = Additional information
yy = Fault number
x
= Axis identifier (0 = fault is not axis−related)
AIF = Axis interface