5. Controlling the SPC200

5−8

Festo P.BE−SPC200−EN en 0901d

Quitting a fault

If a fault occurs during the program processing, the READY
output will be reset automatically. When the fault has been
eliminated, the fault message can be acknowledged with a
START signal. If several faults occur simultaneously, quitting
must be undertaken several times.

Fault
message

0

1

0

1

0

1

0

1

0

1

ENABLE

READY

STOP

START/CLK

1

2

3

4

3

0

1

Fault

1

Time requirement depends on equipment fitted on the system and whether
there are faults (max. 10 s)

2

Debounce time t

≥ 10 ms

3

Quitt. faults; if there are several faults, quitt. must be undertaken several times

4

Start program or NC record

Fig. 5/3:

Time behaviour when quitting a fault

If there are no faults, the READY output will supply a 1−signal
again. Then program sequence can then be continued or the
next NC record can be started.