8. Diagnosis and error treatment
8−21
Festo P.BE−SPC200−EN en 0901d
Fault class 5:
Sequence control fault
Fault
stage
Fault
message
Operating status / fault explanation
Eliminating faults
C
ppp01x05
Starting program does not exist
·
Correct starting program
number or load/enter
starting program
nnn02x05
Sub−program does not exist (L command)
·
Correct NC record or load/
enter program
nnn03x05
NC record does not exist
·
Correct NC record
nnn04x05
Program no. with L command is identical to
number of the accessing program
·
Correct NC record
nnn05x05
Permitted nesting depth with L command
exceeded
·
Correct NC record
nnn06x05
Direct nominal value specification (M10) or
direct control of the valve voltage (M39)
active with new nominal value (NC comĆ
mand: G00, G01, G02, M10, M39)
·
Correct the NC record, first
conclude direct nominal
value specification or direct
control of the valve voltage
with M12.
nnn07x05
Arithmetical overrun with a register (R)
·
Correct NC record
nnn08x05
Record overrun
·
Conclude NC programs with
command M02 or M30
nnn09x05
nnn0Ax05
Reserved
zzz0Bx05
NC command cannot be processed. Either it
is not supported by the firmware or the axis
specification is not valid.
·
Check axis specification
·
Check firmware version
zzz = Additional information
yy
= Fault number
x
= Axis identifier (0 = fault is not axis−related)
ppp = Program number
nnn = NC record number of the accessing NC command