8. Diagnosis and error treatment

8−32

Festo P.BE−SPC200−EN en 0901d

Fault class 8:

NC Editor, Upload/download or operation execution fault

Fault
stage

Eliminating faults

Operating status / fault explanation

Fault
message

D

zzz16x08

Compatibility error between WinPISA and the
operating system version of the SPC200.
zzz = 001: The function Calibration of

operating system version 4.82
requires at least WinPISA 4.41.

·

Use the latest version of
WinPISA; if necessary downĆ
load it from Festo’s downĆ
load area < festo.com> and
use it to carry out the
calibration.

·

Adapt measuring system
length in the Axis data"
dialogue.

zzz = Additional information
yy

= Fault number

x

= Axis identifier (0 = fault is not axis−related)

ppp = Program number

Fault class 9:

Trace fault

Fault
stage

Fault
message

Operating status / fault explanation

Eliminating faults

D

00001x09

Too many trace variables defined.
Max. 10 trace variables per axis are
permitted

·

Check measured value
configuration

00002x09
to
00005x09

Reserved

ć

00006x09

Trace memory reserved for another
axis

·

Create default measured value conĆ
figuration for all axes. Then specify
desired configuration again

00007x09

Unknown trace variable defined
(caused by the use of different
firmware versions)

·

Create and confirm default
measured value configuration.
Then set the desired configuration
again

00008x09

Trace not configured

·

Carry out System Reset

zzz = Additional information
yy = Fault number
x

= Axis identifier (0 = fault is not axis−related)