8. Diagnosis and error treatment
8−29
Festo P.BE−SPC200−EN en 0901d
Fault class 7:
Fault in the pre−parametrizing
Fault
stage
Eliminating faults
Operating status / fault explanation
Fault
message
C
zzz0Dx07
Configured assignment of a local I/O range
to the specified field bus I/O range in the
SPC200 is not permissible because the
local module itself is not present.
zzz = I/O word no.:
000: Assignment to IW11 faulty
001: Assignment to IW12 faulty
002: Assignment to IW13 faulty
003: Assignment to QW11 faulty
004: Assignment to QW12 faulty
005: Assignment to QW13 faulty
·
Correct the configuration;
see description of the field
bus module or the configurĆ
ation menu of WinPISA from
version 4.41.
zzz0Ex07
Configured assignment of a local I/O range
to the specified field bus I/O range in the
SPC200 is not permissible because the
field bus I/O range is already occupied.
zzz = I/O word no.:
000: Assignment to IW11 faulty
001: Assignment to IW12 faulty
002: Assignment to IW13 faulty
003: Assignment to QW11 faulty
004: Assignment to QW12 faulty
005: Assignment to QW13 faulty
·
Correct the configuration;
see description of the field
bus module or the configurĆ
ation menu of WinPISA from
version 4.41.
Please note: Each local I/O
range may be assigned only
once.
zzz = Additional information
yy = Fault number
x
= Axis identifier (0 = fault is not axis−related)