6. Operating the SPC200 with the control panel
6−53
Festo P.BE−SPC200−EN en 0901d
Menu TEST/DIAG. (test and diagnosis)
Sub−menu SYSTEM
SINGLE STEP
P00
Program test in single steps
P00 ... P99
(only supported in Start/Stop mode)
With this function you can test an existing program in single−step mode.
Proceed as follows:
1. Set the program number.
2. Press the Enter button to confirm the selection.
3. Press the Enter button to start the NC record.
4. Repeat point 3 in order to start the next NC record.
INPUT TEST
I0.00:0
Input test
1)
I = input
I0.00 ... I5.15.
With this command you can test the inputs of the system to make sure
that they function. The input signal entered fades out the real signal
and is taken into account for sequence control (e.g. Start/Stop) as well
as for the program sequence. Thereafter the actual input signal is valid
once again.
FB INPUT TEST
I10.00:0
Test field bus inputs
1)
I = input
I10.00 ... I13.15.
OUTPUT TEST
Q0.00:0
Output test
1)
Q = output
Q0.00 ... Q5.15
The READY output and the ACK outputs used by the system are
permanently updated by the operating system and cannot therefore be
influenced.
FB OUTPUT TEST
Q10.00:0
Test field bus outputs
1)
Q = output
Q10.00 ... Q13.15
FLAG TEST
F00:0
Test flags
1)
F = flag
F00 ... F63
REGISTER TEST
R00:0
Test register
1)
R = register
R00 ... R99
1)
With this command the status of the relevant operand can be modified.