12.1 Troubleshooting

12.1.3 LED Indicators (MP2200/MP2300)

12-5

Troubleshooting

Errors

Not lit Not lit

Not lit

Lit

Not lit

A serious error has occurred.

Refer to 12.2.3 Correcting User Pro-
gram Errors
.

No lit

Not lit

Lit

Not lit

Not lit

Not lit Not lit

Not lit

Blinking Not lit

Software Error
Number of LED blinks indicates error
type.
3: Address error (read) exception
4: Address error (write) exception
5: FPU exception
6: Illegal general command exception
7: Illegal slot command exception
8: General FPU inhibited exception
9: Slot FPU inhibited exception
10: TLB multibit exception
11: LTB error (read) exception
12: LTB error (write) exception
13: LTB protection violation (read)

exception

14: LTB protection violation (write)

exception

15: Initial page write exception

A hardware error has occurred.
Replace the Module.

Not lit Not lit Blinking Blinking Not lit

Hardware Error
Number of LED blinks indicates error
type.
2: RAM diagnostic error
3: ROM diagnostic error
4: CPU function diagnostic error
5: FPU function diagnostic error

Warnings

-

-

-

-

Lit

Battery alarm

Replace the battery to save the mem-
ory.

Lit

Lit

Lit

Not lit

Not lit Operation error

I/O error

Refer to 12.2.4 ( 3 ) Ladder Program
User Operation Error Status
and
12.2.4 ( 4 ) System Service Execution
Status
.

(cont’d)

Classification

LED Indicator

Indicator Details

Countermeasures

RDY

RUN

ALM

ERR

BAT