4.4 MP2000 Series Machine Controller Parameter Details
4.4.2 Motion Setting Parameter Details
4-31
Motion Parameters
• Operation
To repeat latch operations, set bit 4 of OW
00 to 1.
For usual latch operations, IW
44 and IW
45 are set to 0.
[ c ] Continuous Latch Operation
For continuous latch operations, bit 2 of IW
0C is set to 0. With this setting, however, the parameters IL
18,
IW
44, and IW
45 are updated when latching, so the completion of latching can be checked with those parame-
ters.
If checking the completion with bit 2 of IW
0C, reset the bit settings with the following procedures.
• The same timing is required to change the bit settings: Change bit 10 of OW
00 from 1 to 0 at the same
moment as bit 2 of IW
0C turns ON.
Precautions
When continuous latching is done for a short time, the sign of latch completion may not be detected because the update of the
communication cycle or H scan cycle is delayed.
To check if the latch was successfully completed, use IW
44 or IW
45.
If the current value is one greater than that of the previous cycle, then latching was successfully completed.
Example 1
• Condition: Latch at phase-C pulse
• Settings:
Motion setting parameters
* When using a continuous latch, the settings of bits 0 to 3 are disabled.
Servo parameters
A square ( ) indicates an unspecified value.
Machine Coordinate
System Latch Position
IL
18
Number of Continuous
Latch Sequence
Completion Cycles
IW
45
Latch Completion
Sequence Number
IW
44
Latch Complete
IW
0C.bit 2
Latch Mode
IW
00.bit 4
Latch Detection Demand
OW
00.bit 4
0
0
Latch
Latch
Register No.
Name
Setting value
OW
01
Mode Setting 1
Bit 6: Latch mode selection = 1 (Continuous latch)
OW
04
Function Setting 2
Bits 0 to 3: Latch detection signal selection = Disabled
*
Parameter No.
Name
Setting value
Pn850
Latch Sequence Number
1
Pn851
Continuous Latch Count
0 (No limit)
Pn852
Latch Sequence Signal 1 to 4 Setting
0h
Pn853
Latch Sequence Signal 5 to 8 Setting
h