5 read fixed parameters (fixprm_rd), 1 ) executing/operating procedure, 2 ) related parameters – Yaskawa MP2000 Series: Built-in SVB or SVB-01 Motion Module User Manual
Page 269

6.4 Motion Subcommand Details
6.4.5 Read Fixed Parameters (FIXPRM_RD)
6-108
6.4.5 Read Fixed Parameters (FIXPRM_RD)
The FIXPRM_RD command reads the current value of the specified fixed parameter and stores the value in the Fixed
Parameter Monitor monitoring parameter.
( 1 ) Executing/Operating Procedure
1.
Check to see if all the following conditions are satisfied.
2.
Set OW
0A to 5 to execute the FIXPRM_RD motion subcommand.
The FIXPRM_RD will read the specified fixed parameter’s current value and store the code in the monitoring
parameter.
IW
0A will be 5 during command execution.
IW
0B, bit 0 will turn ON during the command processing and will turn OFF when the command processing
has been completed.
3.
Set OW
0A to 0 to execute the NOP motion command and then complete the monitoring operation.
( 2 ) Related Parameters
[ a ] Setting Parameters
[ b ] Monitoring Parameters
R
No.
Execution Conditions
Confirmation Method
1
Motion subcommand execution has been completed.
IW
0A is 0 and IW
0B, bit 0 is OFF.
Parameter
Name
Setting Contents
SVR
OW
0A
Motion Subcommand
The Read Fixed Parameter subcommand is executed when this parameter
is set to 5.
OW
5C
Fixed Parameter Number
Set the parameter number of the fixed parameter to be read.
Parameter
Name
Monitoring Contents
SVR
IW
0A
Motion Subcommand
Response Code
Indicates the motion subcommand that is being executed.
The response code is 5 during FIXPRM_RD command execution.
IW
0B
Bit 0
Command Execution
Flag
Turns ON during FIXPRM_RD command execution and turns OFF when
execution has been completed.
IW
0B
Bit 3
Command Error
Completed Status
Turns ON if an error occurs during FIXPRM_RD command execution. Turns
OFF when another command is executed.
IW
0B
Bit 8
Command Execution
Completed
Turns ON when FIXPRM_RD command execution has been completed.
IL
56
Fixed Parameter
Monitor
Stores the data of the specified fixed parameter number.
R
R
R
R
R
R
R