10.3 Main Commands and Subcommands

10.3.4 Subcommand Details

10-24

( 4 ) Write User Constant

Description

Writes the specified inverter user constant in the Inverter internal constant.

Valid only in MECHATROLINK-II 32-byte mode.
With Varispeed G7 and F7, it is necessary to execute the command User Constant RAM Writing (see 10.3.3 ( 7 )
User Constant RAM Writing
) to validate the data written by executing Write User Constant.
With VSminiV7, the data written by executing Write User Constant will be immediately validated.

Setting Parameters

Monitoring Parameters

Name

Register No.

Setting Range

Remarks

Subcommand Code

OW

0A

0 to 9

03: Write User Constant

Auxiliary Inverter Constant Number

OW

42

0 to FFFFh

Auxiliary Inverter Constant Number
Size

OW

43

1 to 4

Data type: Word (Enter the size of user constant
that read out from the leading user constant
number of the auxiliary inverter.)

Auxiliary Inverter User Constant
Set Point 1

OW

44

0 to 65535

Auxiliary Inverter User Constant
Set Point 2

OW

45

0 to 65535

Auxiliary Inverter User Constant
Set Point 3

OW

46

0 to 65535

Auxiliary Inverter User Constant
Set Point 4

OW

47

0 to 65535

Name

Register No.

Setting

Range

Remarks

Subcommand Response Code

IW

0A

0 to 9

03: Write User Constant

Subcommand Status

IW

0B

Bit

Bit 0 (Command execution flag)

ON during execution

Bit 3 (Command error completed
status)

ON when an error
occurs during com-
mand processing.

Bit 8 (Command execution com-
pleted)

ON when the com-
mand execution is
completed.

Subcommand Response Status

IW

31

Bit

Refer to Subcommand Response Status of 10.4.3 Monitor-
ing Parameter List
.

Response Alarm Code

IW

30

0 to FFFFH

Inverter alarm code

Inverter User Constant No.

IW

3C

0 to FFFFH