5 ) alarm monitor, 6 ) alarm history monitor – Yaskawa MP2000 Series: Built-in SVB or SVB-01 Motion Module User Manual
Page 382

10.3 Main Commands and Subcommands
10.3.3 Command Details
10-18
Monitoring Parameters
( 5 ) Alarm Monitor
Description
Reads the alarm that is occurring in the Inverter.
Setting Parameters
Monitoring Parameters
( 6 ) Alarm History Monitor
Description
Reads the Inverter alarm history.
Setting Parameters
Name
Register No.
Setting
Range
Remarks
Command Response Code
IW
08
0 to 8
03: Write User Constant
Command Status
IW
09
Bit
Bit 0 (Command execution flag)
ON during execution
Bit 3 (Command error completed
status)
ON when an error
occurs during com-
mand processing
Bit 8 (Command execution com-
pleted)
ON when command
execution is com-
pleted.
Status
IW
10
Bit
Inverter status
Response Alarm Code
IW
30
0 to FFFFH
Inverter alarm code
Inverter User Constant Number IW
3C
0 to FFFFH
Name
Register No.
Setting Range
Remarks
Command Code
OW
08
0 to 8
04: Alarm Monitor
Name
Register No.
Setting
Range
Remarks
Command Response Code
IW
08
0 to 8
04: Alarm Monitor
Command Status
IW
09
Bit
Bit 0 (Command execution flag)
ON during execution
Bit 3 (Command error completed
status)
ON when an error
occurs during com-
mand processing
Bit 8 (Command execution com-
pleted status)
ON when command
execution is com-
pleted.
Status
IW
10
Bit
Inverter status
Response Alarm Code
IW
30
0 to FFFFH
Inverter alarm code
Inverter Alarm Code
IW
32
0 to FFFFH
The currently occurring alarm is read out
Name
Register No.
Setting Range
Remarks
Command Code
OW
08
0 to 8
05: Alarm History Monitor
Inverter Alarm Monitor Number
OW
32
0 to 3
Alarm monitor number (0 to 3 for Varispeed G7 and
F7, 0 or 1 for VSminiV7)