10.2.5 I/O Options
10-11
Settings for Connecting Inverters
10.2.5 I/O Options
( 1 ) Output Data Options
The parameters OW
13 to OW
16 are for output data options.
These output data options will be available when:
• The Output Data Option Selection (OW
0C) is selected while the command Inverter Drive Control is being
executed.
• The Auxiliary Output Data Option Selection (OW
0E) is selected while the subcommand Inverter I/O Con-
trol is being executed.
( 2 ) Input Data Options
The parameters IW
13 to IW
1F are for input data options.
These input data options will be available when:
• The Input Data Option Selection (OW
0D) is selected while the command Inverter Drive Control is being
executed.
• The Auxiliary Input Data Option Selection (OW
0F) is selected while the subcommand Inverter I/O Control
is being executed.
Data of selected input options can be monitored by using the Input Data Option Selection Monitor (IW
0D) and
Auxiliary Input Data Option Selection Monitor (IW
0F) of the monitoring parameters.
( 3 ) Response Speed of Selected Output and Input Data Options
The response speed for the data selected from Output Data Option Selection, Auxiliary Output Data Option Select,
Input Data Option Selection, and auxiliary Input Data Option Selection depends on the amount of selected data. Nor-
mally, it will be six times slower than that for standard I/O data (always available I/O data).