5 i/o options – Yaskawa MP2000 Series: Built-in SVB or SVB-01 Motion Module User Manual

Page 375

background image

10.2 Operating Inverters Using an MPE720

10.2.5 I/O Options

10-11

Settings for Connecting Inverters

10.2.5 I/O Options

( 1 ) Output Data Options

The parameters OW

13 to OW

16 are for output data options.

These output data options will be available when:

• The Output Data Option Selection (OW

0C) is selected while the command Inverter Drive Control is being

executed.

• The Auxiliary Output Data Option Selection (OW

0E) is selected while the subcommand Inverter I/O Con-

trol is being executed.

( 2 ) Input Data Options

The parameters IW

13 to IW

1F are for input data options.

These input data options will be available when:

• The Input Data Option Selection (OW

0D) is selected while the command Inverter Drive Control is being

executed.

• The Auxiliary Input Data Option Selection (OW

0F) is selected while the subcommand Inverter I/O Control

is being executed.

Data of selected input options can be monitored by using the Input Data Option Selection Monitor (IW

0D) and

Auxiliary Input Data Option Selection Monitor (IW

0F) of the monitoring parameters.

( 3 ) Response Speed of Selected Output and Input Data Options

The response speed for the data selected from Output Data Option Selection, Auxiliary Output Data Option Select,
Input Data Option Selection, and auxiliary Input Data Option Selection depends on the amount of selected data. Nor-
mally, it will be six times slower than that for standard I/O data (always available I/O data).