11 change filter time constant (scc), 1 ) executing/operating procedure, 2 ) holding and aborting – Yaskawa MP2000 Series: Built-in SVB or SVB-01 Motion Module User Manual
Page 219: 3 ) related parameters

6.2 Motion Command Details
6.2.11 Change Filter Time Constant (SCC)
6-58
6.2.11 Change Filter Time Constant (SCC)
The SCC command transfers the setting of the Filter Time Constant (motion setting parameter OW
3A) to the Mov-
ing Average Time or Exponential Acceleration/Deceleration Time Constant in the SERVOPACK and enables the set-
ting.
Always execute the CHG_FILTER command before executing the SCC command. The setting of the servo parame-
ter to be transferred will depend on the set filter type.
MECHATROLINK-II has a function that automatically updates setting parameters if a parameter changes. There is
no need to execute the SCC command with this function. For details, refer to bit A (User Constants Self-writing
Function) in 4.4.1 ( 2 ) Function Selection 1.
( 1 ) Executing/Operating Procedure
1.
Check to see if all the following conditions are satisfied.
2.
Set OW
08 to 12 to execute the SCC motion command.
The parameter to which the value of OW
3A is transferred will depend on the set filter type:
Without filter or with moving average filter: Moving Average Time
With exponential acceleration/deceleration filter: Exponential Acceleration/Deceleration Time Constant
IW
08 will be 12 during command execution.
IW
09, bit 0 will turn ON during the command processing and will turn OFF when the processing has been
completed.
3.
Set OW
08 to 0 to execute the NOP motion command and then complete the change of the linear
deceleration time constant.
( 2 ) Holding and Aborting
The Holds a Command bit (OW
09, bit 0) and the Interrupt a Command bit (OW
09, bit 1) cannot be used.
( 3 ) Related Parameters
[ a ] Setting Parameters
No.
Execution Conditions
Confirmation Method
1
There are no alarms.
Both IL
02 and IL
04 are 0.
2
Pulse distribution has been completed for the SERVOPACK. IW
0C, bit 0 is ON.
3
Motion command execution has been completed.
IW
08 is 0 and IW
09, bit 0 is OFF.
Parameter
Name
Setting
OW
03
Function Setting 1
Set the speed unit, acceleration/deceleration units, and filter type.
OW
08
Motion Command
The filter time constant is changed when this parameter is set to 12.
OW
09
Bit 0
Holds a Command
This parameter is ignored for SCC command.
OW
09
Bit 1
Interrupt a Command
This parameter is ignored for SCC command.
OW
3A
Filter Time Constant
Set the filter time constant for acceleration/deceleration.