10.3 Main Commands and Subcommands

10.3.3 Command Details

10-17

Settings for Connecting Inverters

Monitoring Parameters

( 4 ) Write User Constant

Description

Writes the specified inverter user constant to a constant in the Inverter.

Valid when using MECHATROLINK

-II 17-byte mode and MECHATROLINK-I.

Use the subcommand when using MECHATROLINK

-II 32-byte mode.

With Varispeed G7and F7, it is necessary to execute the command User Constant RAM Writing (see
( 7 ) User Constant RAM Writing) to validate the data written by executing Write User Constant.
With VSminiV7, the data written by executing Write User Constant will be immediately validated.

Setting Parameters

Name

Register No.

Setting

Range

Remarks

Command Response Code

IW

08

0 to 8

02: Read User Constant

Command Status

IW

09

Bit

Bit 0 (Command execution flag)

ON during execution

Bit 3 (Command error completed
status)

ON when an error
occurs during com-
mand processing

Bit 8 (Command execution com-
pleted)

ON when command
execution is com-
pleted.

Status

IW

10

Bit

Inverter status

Response Alarm Code

IW

30

0 to FFFFH

Inverter alarm code

Inverter User Constant Number IW

3C

0 to FFFFH

User Constant
Reading Data 1

IW

3E

0 to 65535

User Constant
Reading Data 2

IW

3F

0 to 65535

User Constant
Reading Data 3

IW

40

0 to 65535

User Constant
Reading Data 4

IW

41

0 to 65535

Name

Register No.

Setting Range

Remarks

Command Code

OW

08

0 to 8

03: Write User Constant

Inverter User Constant Number OW

3C

0 to FFFFH

Inverter User Constant Number
Size

OW

3D

1 to 4

Data type: Word (Enter the size of the user constant
read out from the leading user constant number of the
inverter.)

Inverter User Constant
Set Point 1

OW

3E

0 to 65535

Inverter User Constant
Set Point 2

OW

3F

0 to 65535

Inverter User Constant
Set Point 3

OW

40

0 to 65535

Inverter User Constant
Set Point 4

OW

41

0 to 65535