Vertical rack mount using crossbars, Installation summary, Precautions – Carrier Access Access Navigator User Manual
Page 93: Tools and materials, Vertical rack mount using crossbars -11, Caution
![background image](/manuals/63313/93/background.png)
Access Navigator - Release 1.8
August 2003
5-11
Physical
Installation
Vertical Rack Mount Using Crossbars
Vertical Rack Mount Using Crossbars
Installation Summary
n
n
n
n
Attach Mounting Brackets to Access Navigator
n
Attach Access Navigator to Crossbars
Precautions
CAUTION!
NEBS
THERMAL
RESTRICTION
– D
O
NOT
INSTALL
MORE
THAN
THREE
ROWS
OF
A
CCESS
N
AVIGATORS
PER
EQUIPMENT
RACK
.
CAUTION!
A
CCESS
N
AVIGATOR
REQUIRES
AT
LEAST
0.75
INCH
OF
FREE
AIR
SPACE
ON
LEFT
AND
RIGHT
SIDE
OF
CHASSIS
FOR
AIR
CIRCULATION
. I
NSUFFICIENT
SPACING
MAY
CAUSE
SERVICE
INTERRUPTIONS
,
RESULTING
FROM
EQUIPMENT
OVERHEATING
AND
SHUTTING
DOWN
. I
F
INSTALLING
MORE
THAN
ONE
ROW
OF
UNITS
,
ENSURE
THAT
UNITS
ARE
MOUNTED
DIRECTLY
ABOVE
OR
BELOW
UNITS
IN
OTHER
ROWS
TO
MAINTAIN
UNOBSTRUCTED
VERTICAL
AIR
CIRCULATION
.
Tools and Materials
Obtain the following tools and materials:
•
Phillips screw drivers, #2 and #3
•
Vertical Mount Crossbars (2 per kit), PN 710-0003 for 19-inch racks
or PN 710-0004 for 23-inch racks.
•
Universal rack mounting kit, PN 710-0153, included with Access Navigator
•
Rack mounting screws (4 ea.), as appropriate for equipment rack
NOTE:
Crossbars are sold in pairs. Two 19-inch crossbars mount in 19-inch equipment
rack and hold up to five Access Navigator or Wide Bank 28 units. Two 23-inch crossbars
mount in 23-inch equipment rack and hold up to six units. One additional crossbar is
needed for each additional row of units.